Specifications; Connections; Insulation Between Interfaces; Climatic Environment - Westermo RD-48 HV Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

4. Specifications

4.1 Connections

Power interface
Model description
Rated voltage
Operating voltage
Rated current
Rated frequency
Polarity
Connection
Connector size
Fuse
RS-422/485 interface – Line A
Electrical specification
Data rate
Connection
Connector size
Circuit type
RS-422/485 interface – Line B
Electrical specification
Data rate
Connection
Connector size
Circuit type

4.2 Insulation between interfaces

Power (RD-48 HV) to all other
Power (RD-48 LV) to all other
Line-A to Line-B

4.3 Climatic environment

Temperature, operating
Temperature, storage and transportation
Relative humidity, operating
Relative humidity, storage and transportation
6153-2004
RD-48 LV RD-48 LV TEMP
12–48 VDC
9.6–57.6 VDC
300 mA
Reverse polarity protected
2-position screw terminal
0.2 – 2.5 mm² (AWG 24-12)
To be externally fused.
RS-422/485
300 bit/s – 1.5 Mbit/s
4-position screw terminal
0.2 – 2.5 mm² (AWG 24-12)
TNV-1
RS-422/485
300 bit/s – 1.5 Mbit/s
4-position screw terminal
0.2 – 2.5mm² (AWG 24-12)
TNV-1
3.0 kV RMS @ 50Hz and 60 s duration
1.0 kV RMS @ 50Hz and 60 s duration
1.5 kV RMS @ 50Hz and 60 s duration
95–240 VAC
110–250 VDC
85.5–264 VAC
88–300 VDC
Polarity independent
3-position screw terminal
5 to 55°C
–40 to 70°C (TEMP version)
–40 to 70°C
5 to 95% (non-condensing)
5 to 95% (condensation allowed
outside packaging)
RD-48 HV
50 mA
48–62 Hz
17