D. INSTALLATION.
General
The control unit is supplied with 5 meters cables in flexible conduit.
The user should connect only the line supply cable through PG 13.5 gland.
Paragraph 2 & 3 are for user knowledge in case of cables extension or rewiring.
1. Connect the line supply cable (4x1-1.5mm) to the control unit terminals
IMPORTANT ! Line supply MUST be protected by 3x4 or 6 amp. Circuit breakers.
TB GND – GND wire.
TB1 - N. Natural wire.
TB2 - Live L1 phase. (Trough 4-6amp. Circuit breaker)
TB3 - Live L2 phase. (Trough 4-6amp. Circuit breaker)
TB4 - Live L3 phase. (Trough 4-6amp. Circuit breaker)
2. Connect the motor line supply cable , using 4x1-1.5mm cable, between the control
unit and filter connection box Terminals
Control board
TB5 - Motor GND. Wire
TB6 - Motor U phase wire
TB7 - Motor V phase wire
TB8 - Motor W phase wire
IMPORTANT ! Verify good connection to MOTOR GROUND!
Check again that the motor operating voltage connection (triangle/star) is
compatible with line supply voltage applied ,and that the overload (OL1) is
adjusted according to the motor nominal current consumption with the voltage
applied.
Filter Junction box
yellow/green
(1)
(2)
(3)
AF900
TB5
TB
TB7
TB8