Installation dimensions

Before installation of the Geberit Mapress
ball valve, it must be ensured that the
minimum space requirements L2 are
available for the actuation of the actuator
lever. → See figure.
Table 3: Installation dimensions
d
Minimum space requirements L2
[mm]
[cm]
15
10.5
18
10.5
22
10.5
28
13
35
13
42
16
54
16
76.1
22.5
88.9
36
108
50
16
Installation
Pressing the Geberit Mapress
ball valve
The Geberit Mapress ball valve does
not influence the direction of flow of
the medium. The ball valve can be
installed in any direction of flow and
in any installation position.
Prerequisite
Minimum space requirements L2 is
ensured.
1
Ensure that the Geberit Mapress ball
valve is free of dust and foreign
bodies. Clean with water or steam if
required.
2
Press the connections. → See
installation manual 996.075.00.0
"Processing Geberit Mapress system
pipes" and operating instructions of
the pressing tools used.