Installation • Instalación
1. Feed pipe and fitting at least 1".
(Internal diameter >0.87")
2. No filters in feed line.
3. Slope in feed line >1%.
4. Use ball valves only.
5. Minimum pressure: 12 psig or 18 psig.
(Check type plate for correct pressure)
6. Short pressure hose.
7. For each yard of rising slope in the outlet
line, the required minimum pressure will
increase by 1.5 psig. The rise of the outlet
line must not exceed 17 feet.
8. Minimum collecting line 1" with 1%
slope.
9. Always install a venting line.
10. The upper 3/4" connection should
only be used as a condensate inlet in
exceptional cases since this could lead to
inflow problems.
8
Quincy Compressor-Q MAT 06 Condensate Drain
1. Tubería de entrada y piezas de conexión
mín. ¾" (o 1"). (Diámetro interior >22mm)
2. No ponga ningún filtro en la tubería de
entrada.
3. La tubería de la entrada tiene que tener
una pendiente descendente constante
>1%.
4. Utilice solamente llaves de paso esféricas
5. Presión de funcionamiento mín. 0,8 bar
o 1,2 bar (lea la presión indicada en la
etiqueta de identificación).
6. Tubo a presión corto.
7. Por cada metro que asciende la tubería
de salida, se incremento la presión
mínima de funcionamiento en 0,1 bar.
Subida máxima de la tubería de salida:
5m
8. Tubería colectar de los condensados: mín.
1" con pendiente descendente constante
1%.
9. Instalar siempre una conducción de
ventilación.
10. Utilizar la conexión superior de ¾'' como
alimentación de condensado solamente
en casos excepcionales, ya que podrían
producirse problemas de alimentación.