Description AQUA 3000 open

The thermal disinfection of a group of fittings is started automatically by actuating the
electronic modules.
The sequence of thermal disinfection is controlled and recorded by the ECC function
controller or the system software.
Carrying out the thermal disinfection
Warning!
• The power supply, consisting of the residual current safety device (RCD), mains
unit and controller must be installed in a separate room outside the wetroom.
• The local accident prevention regulations (UVV) must be observed.
Failure to observe this instruction can result in injuries due to scalding.
Fittings-dependent setting of the scald protection or temperature limit stop, before
and after the flushing process, is not necessary.
Start the thermal disinfection.
9.1
• The bypass solenoid valve cartridges of a fittings group open up.
• Unmixed hot water flows into the shower cubicle via the shower head (volume
flow = 0.06 l/s). The flushing temperature corresponds to the temperature in the
circulation line.
• After thermal disinfection, the remaining hot water (>45 °C) is drained from each
shower fitting. This is done by automatically triggering each fitting.