AEG SNMP Manuel D'installation page 3

Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

Installation/Network Integration of a SNMP Adapter
1. Enabling of configuration mode
Variant 1
1.
Move the Slide Switch in the middle position / DIP
SW 1 & 2 in the position OFF.
2.
Connect the
LAN
port of the SNMP Adapter di-
rectly with an
Ethernet Cross Cable
workstation.
Important:
It is recommended to set the PC to the same network
segment, for example 10.10.10.11 AND for the Gate-
way 10.10.10.11 .
Variant 2
1.
Move the Slide Switch in the middle position / DIP
SW 1 & 2 in the position OFF.
2.
Connect the PC with a Switch or Hub and
Network Cables
on the
2. Connect device to the UPS
External Version
Connect the UPS with the original UPS cable to the
COM1
port of the SNMP Adapter.
Slot Version
Put the device into the
For the installation of the UPS, have a look into the
User Manual which is part of the documentation CD
or could be downloaded from the homepage of your
UPS manufacturer.
All UPS functions and the usage of flexible events
etc. are described in the SNMP Adapter User Ma-
nual!
3. Connect the SNMP Adapter to the power supply
External Version
Connect the SNMP Adapter to the provided power
supply.
Slot Version
The slot devices are supplied via the slot interface of
the device. It is always possible to insert or remove
the SNMP Adapter without damaging the UPS. To
interrupt the power supply, remove the device from
the slot and insert it again.
to the PC /
LAN
port of the device.
slot interface
of the UPS.
IP 10.10.10.10
DIP Switch 1+2 = off
Slide Switch „middle"
two
IP 10.10.10.10
DIP Switch 1+2 = off
Slide Switch „middle"
Ethernet
cross
IP: 10.10.10.11
cable
Subnet: 255.255.255
Gateway: 10.10.10.11
Ethernet
cables
IP: <Your IP Address>
Gateway: <Your Gateway>
Hub/Switch
Power Supply
English

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Snmp-proSnmp-mini

Table des Matières