Wiring the SD-7202GC-PEQ and SD-7223GW-LQ:
1. Run four wires through the wall to a single-gang back-box
as follows:
a. Two wires from a 12VDC or 24VDC power source for
the pushbutton light.
b. One wire from either the NO or NC terminal of a device
such as an alarm or access control system which can
unlock an electrically-controlled lock.
c. One wire from the COM terminal of that device.
2. Connect the included colored wires to the switch
(see Fig. 5):
a. To power the pushbutton's LED, connect 1 GREEN wire to each of the brass-colored spade
connectors on the sides of the black switch.
b. Connect GREEN/WHITE wire to the N.C. connector on the black switch (if needed).
c. Connect BLUE/WHITE wire to the N.O. connector on the black switch (if needed).
d. Connect WHITE wire to the COM connector on the black switch.
3. Connect the colored wires to wires from the alarm or access control system and the light's power
source (see Fig. 5):
a. 2x GREEN wires – To a 12 or 24 VDC source. The polarity of the LED must be observed.
b. GREEN/WHITE wire – To the N.C. terminal of the alarm or access control system (if needed).
c. BLUE/WHITE wire – To the N.O. terminal of the alarm or access control system (if needed).
d. WHITE wire – To the COM terminal of the alarm or access control system.
4. Screw the plate onto the back-box, taking care not to crimp the wires.

IMPORTANT

Users and installers of this product are responsible for ensuring that the installation and configuration of this
product complies with all national, state, and local laws and codes related to locking and egress devices.
SECO-LARM will not be held responsible for the use of this product in violation of any current laws or codes.
Wiring the SD-7202GC-PTQ (with timer module):
1. To power the pushbutton's LED, connect 1 GREEN
wire to each of the brass-colored spade connectors on
the sides of the black switch and bulb assembly (see
Fig. 5 above) and connect the other side of each
GREEN wire to a 12 or 24 VDC source. The polarity of
the LED must be observed.
2. Connect 12 or 24 VDC (non-polarized) to the power input
terminals of the timer module (see Fig. 6).
3. Connect an N.O. or N.C. device, such as an
electromagnetic lock or alarm, to the relay output
terminal block as desired (3A@24VDC max.).
4. Connect buzzer to the buzzer output terminal if desired.
5. Set the time of the timer module between 1~180 sec via
the trimpot. Turn clockwise to increase and
counterclockwise to decrease. Test to ensure the timer
is set correctly.
SECO-LARM U.S.A., Inc.
ENFORCER Pushbutton Request-to-Exit Plates
Figure 5
Green wires (light)*
(12VDC or 24VDC)
White wire (COM)
Max. 10A@125~250 VAC
Blue/white wire (N.O.)
(Lug farthest from plate)
Green/white wire (N.C.)
(Lug closest to plate)
*The polarity of the LED must be observed.
Figure 6
Timer
To adjust time (1~180 sec), turn
Adjustment
trimpot clockwise to increase,
Trimpot
counterclockwise to decrease.
(–)
(+)
(N.C.)
(N.O.)
(COM)
(COM)
(N.C.)
(N.O.)
Note: Terminal legend can be found on back of PCB.
+
(–)
(
)
Buzzer
Output
Relay Output
(3A@24VDC)
Trigger Input
(Factory prewired)
Power Input 12 or 24
VDC (non-polarized)
3