ThermoKey Wet Fin Systems Manuel Technique page 8

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

ThermoKey
Heat Exchange Solutions
TC 7. Configurations
JUMBO "N" SERIES (MODULE 1250MM) [JW/JG/JKX2XXN EX JGH2810CN]
Water enters through a 1/2" male inox pipe union (in absence of pump) [3/4" only for special cases].
§
§
The number of nozzles for standard units is 2 for the coil module for each rack.
§
§
The Number of nozzle ramp for each coil is 3 for all configurations.
§
§
The nozzles are made in POM (U05 type) and oriented in airflow direction.
§
§
JUMBO "Z" SERIES (MODULE 2000MM) [JW/JG/JKX2XXZ EX JGH2510CZ]
Water enters through a 1/2" male inox pipe union (in absence of pump) [3/4" only for special cases].
§
§
The number of nozzles for standard units is 3 for the coil module for each rack.
§
§
The Number of nozzle ramp for each coil is 3 for all configurations.
§
§
The nozzles are made in POM (U05 type) and oriented in airflow direction.
§
§
SUPERJUMBO (MODULE 1200MM) [SJW/JG/JKX2XX EX SJGH2890C]
Water enters through a 1/2" male inox pipe union (in absence of pump) [3/4" only for special cases].
§
§
The number of nozzles for standard units is 2 for the coil module for each rack.
§
§
The Number of nozzle ramp for each coil is 3 for all configurations.
§
§
The nozzles are made in POM (U05 type) and oriented in airflow direction.
§
§
MINIJUMBO "N" SERIES (MODULE 1400MM) [JW/JG/JKX1XXN EX JGH1710CN]
Water enters through a 1/2" male inox pipe union (in absence of pump) [3/4" only for special cases].
§
§
The number of nozzles for standard units is 2 for the coil module for each rack.
§
§
The Number of nozzle ramp for each coil is 2 for all configurations.
§
§
The nozzles are made in POM (U05 type) and oriented in airflow direction.
§
§
MINIJUMBO "Z" SERIES (MODULE 2100MM) [JW/JG/JKX1XXZ EX JGH1510CZ]
Water enters through a 1/2" male inox pipe union (in absence of pump) [3/4" only for special cases].
§
§
The number of nozzles for standard units is 3 for the coil module for each rack.
§
§
The Number of nozzle ramp for each coil is 2 for all configurations.
§
§
The nozzles are made in POM (U05 type) and oriented in airflow direction.
§
§
NOTES
Configuration of unit with spray system can change from standard: please take into consideration adiabatic configuration
§
§
of approval drawing of unit.
The unit is supplied complete with all its parts mounted: should the upper ramps result turned downwards (or demounted)
§
§
it is for the scope of meeting the maximum acceptable dimensions of the unit for transportation.
If required, the customer can rotate the entire ramp since they are connected by joints that enable this rotation:
§
§
ThermoKey can answer on matters of nebulization efficiency of the adiabatic system only when in standard configuration
(with nozzle defined by ThermoKey and with installation defined by ThermoKey).
13
MT TC R WFS EN 03 2018
TC 8. Materials
Most sensitive part concerning the promotion of microbiological growth is the coated heat exchanger. Causal for possible
proliferation is:
For some species the polymer coating can be a possible food source.
§
§
The heat exchanger is wet nearly complete with spray water.
§
§
While passing the heat exchanger, the water is warmed up.
§
§
Dirt from the air intake can be caught in the fins of the heat exchanger and is also a possible food source.
§
§
Due to uncorrected make up of the spray water deposition of lime (scaling) can occur.
§
§
Therefore the following actions on the heat exchanger must be done and documented regularly:
Position
Inspection for
Frequency
Action to be done by indication
1
Microbiological growth
Monthly
Mechanical cleaning* and disinfection**
2
Dirt from air intake
Monthly
monthly Mechanical cleaning*
3
Scaling
Monthly
Mechanical cleaning* and control of the spray water quality
4
Spray nozzles
Monthly
Mechanical cleaning or exchange
5
Damage
Half a year
Reparation in accordance with ThermoKey
6
Corrosion
Monthly
Reparation in accordance with ThermoKey
* Methods for mechanical cleaning:
Soft brush.
§
§
Compressed air, maximum pressure: 2 bar.
§
§
Water, maximum pressure: 2 bar.
§
§
To prevent a deformation of the fins, the air and water jet must be directed vertical those, at a minimum distance of
200 mm.
** Disinfection agents: Bacillol AF.
MT TC R WFS EN 03 2018
Technical Manual TC Instruction and technical data
14

Publicité

Table des Matières
loading

Produits Connexes pour ThermoKey Wet Fin Systems

Ce manuel est également adapté pour:

Wfs

Table des Matières