Kemper KHS CoolFlow 615 0G Manuel D'utilisation page 19

Masquer les pouces Voir aussi pour KHS CoolFlow 615 0G:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

1
Technical data
Servo drive
Power supply
Power consumption dimensioning
Power consumption nominal
Max. inrush current
Connection cable length
Cable cross-section
Max. ambient temperature
Max. ambient humidity
Overvoltage category
Actuating force
Contamination level
Protection class in acc. with EN 60730
Max. valve stroke
Actuator time
Note!
The minimum cycle time in 3-point mode is 2 seconds. If the drive has a
shorter switch-on time, a correct switch-off cannot be guaranteed.
© www.kemper-olpe.de – 06.2020 – K410061500001-00 – 19 /72
Fig. 615 0G (230 V)
230 V AC
(50/60 Hz)
5,8 VA
3,5 VA
Briefly max. 10 A
1,5 m
3 x 0,75 mm²
50 °C
0 - 85 % (non-condensing)
220 N
2
9 mm (valve stroke can be read on position indicator)
15 s/mm
Fig. 616 0G (24 V)
24 V AC
24 V DC
(50/60 Hz)
4,7 VA
2,2 W
2,5 VA
1,3 W
5 x 0,5 mm²
III
2
3