Wilo -EFC0.37 3x380-480V 50/60Hz IP55 Notice De Montage page 76

Table des Matières

Publicité

Spécifications
Boîtier
Puissance [kW
(HP)]
A2
1,1–4,0
(1,5–5)
A3
5,5–7,5
(7,5–10)
A4
1,1–4,0
(1,5–5)
A5
1,1–7,5
(1,5–10)
B1
11–18,5
(15–25)
B2
22–30
(30–40)
B3
11–18
(15–24)
B4
22–37
(30–50)
C1
37–55
(50–75)
C2
75–90
(100–125)
C3
45–55
(60–75)
C4
75–90
(100–125)
Tableau 8.20 380-480 V, tailles de boîtier A, B et C
MG21L104
Manuel d'utilisation
Taille de fusible
Fusible max.
recommandée
recommandé
gG-10 (0,37-3)
gG-16 (4)
gG-16
gG-10 (0,37-3)
gG-16 (4)
gG-10 (0,37-3)
gG-16 (4-7,5)
gG-40
gG-50 (18,5)
gG-63 (22)
gG-40
gG-50 (18,5)
gG-63 (22)
gG-80 (30)
gG-80 (30)
gG-100 (37)
gG-160 (45)
aR-200 (55)
aR-250 (75)
gG-100 (37)
gG-150 (37)
gG-160 (45)
gG-160 (45)
aR-200 (55)
aR-250 (75)
10/2017 Tous droits réservés.
Disjoncteur
recommandé
Moeller
gG-25
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-32
PKZM0-25
gG-80
PKZM4-63
gG-100
NZMB1-A100
gG-63
PKZM4-50
gG-125
NZMB1-A100
gG-160
NZMB2-A200
aR-250
NZMB2-A250
NZMB2-A200
aR-250
NZMB2-A250
Seuil de déclen-
chement max. [A]
25
25
25
25
63
100
50
100
160
8
250
150
250
75
8