Install The Drain Pipe - Fujitsu Airstage ARXD07GALH Manuel D'installation

Masquer les pouces Voir aussi pour Airstage ARXD07GALH:
Table des Matières

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 42
(1) Ceiling concealed type
100 mm or more
Locally arranged pipe
Observe the following procedures to construct centralized drain pipe fi ttings.
VP30 or more
[O.D 38 mm or more]
(2) Wall mounted type/Floor standing concealed type
Locally arranged pipe
Observe the following procedures to construct centralized drain pipe fi ttings.
VP30 or more
[O.D 38 mm or more]
En-9
9374342273-01_IM.indb Sec1:9
9374342273-01_IM.indb Sec1:9
Gap of 1.5 to 2 m
Downward gradient
2.5 to 5.0 mm
Supporter
VP25 [O.D 32 mm
or more]
Good
Air bleeding
Trap
Rise
Prohibited
Downward gradient
1/100 or more
Downward gradient
2.5 to 5.0 mm
100 mm
VP25 [O.D 32 mm
or more
or more]
Good
Air bleeding
Trap
Rise
Prohibited
Downward gradient 1/100
or more

5.2. Install the drain pipe

(1) Be sure to use supplied Drain hose 1 and Hose band 2
2 Hose band (Accessories)
Drain
hole
Hose band
4 mm or less
20 mm
1 Drain hose
Fasten the Hose band 2 at the position where
horizontal against earth (ground).
The Hose band 2 must be positioned at the right
side of the Drain hose
1
(2) Be sure to connect Drain pipe with adhesive (polyvinyl chloride) so that there is no
leakage.
CAUTION
Do not connect to the Drain hole with adhesive. Using adhesive may cause damage
and water leaks.
(3) After installing the Drain hose 1 , check if the drainage is smooth.
CAUTION
To prevent excessive force on Drain hose 1, avoid bends or twists. (To bend or twist
may cause water leaks.)
(4) After checking for drainage, attach the Drain hose insulation B 3 to insulate, following
the instructions as in the fi gures.
To avoid space with Drain hose 1 and Hose band 2 , press fi rmly the Drain hose
insulation B 3 .
Ensure there is
no space.
1 Drain hose (Accessories)
Hard PVC side
2 Hose band
as in the fi gure.
Applying
Joint pipe
area of
(Field supply)
adhesive
Drain pipe (VP25)
(Field supply)
4 mm or less
3 Drain hose insulation B
(Accessories)
7/12/2012 10:19:33 AM
7/12/2012 10:19:33 AM