13 Technical specifications

Display range
Display
Display range
Display units with background lighting
Input data
Analogue signal input(s)
Measuring range(s) (up to 3 analogue inputs)
Accuracy class
PT100 input
Measuring range
Accuracy class
Frequency / counter input
Signal threshold
Frequency range
Output data
Analogue output
Accuracy of the analogue output
Rise time
Switching outputs
Type
Switching voltage
Switching current
Switching capacity
Life expectancy of the switching contacts
Reaction time (with switching delay = 0 ms)
Setting range of the switching points
Setting range of the switching hystereses
(switch-back points)
Interface
Ambient conditions
Nominal temperature range
Operating temperature range
Storage temperature range
- mark
Other data
Housing
Electrical connections
Supply voltage
Power consumption
Supply of the measurement transmitter
Protection class to DIN 40050
Reverse polarity protection of the supply
voltage, excess voltage, override protection
Weight
4-digit 7-segment LED display, red, height of digits 14.2 mm
3 LED for active sensor
4 LED for switching relays
- 999..9999 (adjustable by user)
bar, kg/cm², MPa, psi, °C, °F, l/min, mA, V, Hz, kN, m, mm, l, gal,
gal/min, 1/min, and more
adjustable: 4..20 mA, 0..5 V or 0..10 V
≤ ± 0.5 % at 25 °C
- 25..100 °C
≤ ± 0.5 % at 25 °C
0..0.6 V = LOW
3..24 V = HIGH
15 Hz .. 4 kHz
adjustable: 4..20 mA, Ohmic resistance ≤ 400 Ω or
0..10 V, Ohmic resistance ≥ 2 kΩ
≤ ± 0.5 % at 25 °C
70 ms
2 or 4 relays each with separate common supply
0.1..250 VAC
9 mA .. 2 A
400 VA, 50 W (for inductive loads, use varistors)
≥ 20 million at minimum load
≥ 1 million at nominal load
approximately 20 ms
1.5..100 % of the pre-set display range
0.5..99 % of the pre-set display range
Serial interface RS232
Baud rate 19,200 bauds – 8 data bits – 1 start and stop bit –
no parity – no handshake
0 .. + 50 °C
0 .. + 50 °C
- 40 .. + 80 °C
DIN EN 61000-6-1 / 2 / 3 / 4
Control panel housing 96 x 48 x 109 mm
Control panel cut-out 92 (+0.8) x 45 (+0.6) mm
Front panel thickness 1.25.. 5 mm
Maximum installation depth 121 mm
Supply voltage: plug-in terminal block, 2 pole, RM 5.08
Inputs / outputs: plug-in terminal block, 11 pole, RM 3.5
Relays: plug-in terminal block 6 pole, RM 5.08
Max. cross section of the connections 1.5 mm² for inputs / outputs
Max. cross section of the connections 2.5 mm² for supply voltage and
relays
85..265 VAC 50 / 60 Hz or
12..32 VDC
15 VA at 85..230 VAC, fuse protection 1 A inert
12 ± 1 % VDC max. 20 mA per analogue input
IP 20
provided
approximately 320 g