Factory Default: To manually return the unit to factory default settings, press and hold the Push Button for about 15 seconds. This will
return all settings back to factory default with the exception of time delay and light level, which will be set to the current trimpot settings.
When using the FSIR-100 remote to return to factory default (HBP-111 only), all settings will be returned to the original factory settings
regardless of current trimpot positions.
The LED will remain solid ON confirming it has been reset to the factory default.
Cancel: To prevent any changes from being made, hold the push button for about 18 seconds. For example, if resetting to factory
default (or any other setting) is not desired then keep holding until you reach 18 or more seconds. The LED will turn off after 18 seconds
to indicate there were no changes made.
Other Features Available On the HBP-111
Use the FSIR-100 remote to disable or enable following modes:
Burn-In Mode: When Burn-In Mode is invoked the output will turn on for 100 hours and not turn off until 100 hours is reached. But, the
Push Button or remote can turn the load off and the unit will leave Burn-In Mode. Default is Disable.
Walk-Through Mode: In this mode, the load will turn off after a 3 minute period following an initial occupancy event if there is no
detection after the first 30 seconds. If motion continues beyond the first 30 seconds, the set time delay applies. Default is Disable.
Visual Alert: When only 1 minute is left for time delay, the load connected to the relay turns OFF for 1 second. Default is Disable.
Service Mode: In this mode, when Service Mode is disabled, the LED will always be on; both motion detection and light level
functionality are disabled and only the Push Button or remote can toggle load ON and OFF. The default setting for Occupancy Mode is
Enable.
To confirm proper operation, review the Start-Up and Test Mode information.
Red LED on sensor module does not blink:
Check for proper sensor wire connections and make sure they are tightly secured.
Red LED blinks but lights do not turn ON:
1. Make sure that power to the sensor has been ON continuously for at least 60 seconds, then
a. Set daylight set point to maximum and allow the sensor to time out.
b. Turn ON power to the sensor. The load should come ON. If sensor fails to turn ON, continue with step 2.
2. Check power connections to the light fixture.
3. Check all sensor wire connections. Verify the load wire is tightly secured.
Lights will not turn OFF:
1. If there is no motion from people or equipment in the sensor's view but the red LED blinks, look for any nearby source of infrared
energy (heat) in motion, such as turbulent air from a heating or cooling supply, or other sources such as heat from the fluorescent
lamps in the fixture.
• Mount the sensor so that it's lens is below the edge of the fixture and does not directly view the lamps.
• Divert the air supply away from the sensor, or move the sensor.
2. Verify time delay set in trimpot settings. The time delay can be set from 5 minutes to 30 minutes. Ensure that the time delay is set
to the desired delay and that there is no movement within the sensor's view for that time period.
3. Check PIR and Light Level trimpot settings. If all control functions are overridden the load stays ON.
4. Check sensor wire connections. Verify load and neutral wires are secure.
HBP-111-L7
HBP-111-L7-OEM
HBP-111-L7-EM1-OEM
HBP-111-L7-SM1-OEM
HBP-112-L7
HBP-112-L7-OEM
HBP-112-L7-EM1-OEM
HBP-112-L7-SM1-OEM
HBP-L7
HBP-EM1
HBP-SM1
TROUBLESHOOTING

ORDERING INFORMATION

High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens (has remote IR capability)
High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens, bulk (has remote IR
capability)
High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens & Extender, bulk (has
remote IR capability)
High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens & Surface Mount, bulk
(has remote IR capability)
High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens (no remote IR capability)
High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens, bulk (no remote IR
capability)
High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens & Extender, bulk (no
remote IR capability)
High/Low-Bay PIR Sensor 120/230 (Single Phase L-N)/277/347 VAC, White, w/Lens & Surface Mount, bulk (no
remote IR capability)
High/Low-Bay Lens for HBP-11X Series 8ft-40ft Mounting
High/Low-Bay Extender Module for HBP-11X Series
HBP Sensor Surface Mount Module
5

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Wattstopper hbp-111Wattstopper hbp-112

Table des Matières