LEGRAND Wattstopper HBP Série Instructions D'installation page 3

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Using the HBP-SM1 Surface Mount Module
Using the HBP-EM1 Extender Module
Retaining Clip
Extender
Module
WARNING: TURN THE POWER OFF AT THE
CIRCUIT BREAKER BEFORE WIRING.
A 60 second start-up period occurs during initial installation and after a power failure of 5 minutes or more. After applying power, there is
warm-up time of 60 seconds before the sensor begins detecting motion.
• If the HBP powers up with Fail-On mode enabled, the load turns On immediately after power-up. The load stays on during warm-
up. If no motion is detected when warm-up is complete, it waits for the delay time to expire before turning off the load.
• If the HBP is powered up with Fail-Off mode enabled, the load stays off during warm-up time until next motion detection. Once
warm-up is complete, the load turns on when motion is detected.
Setting Time Delay
Using the Trimpot - HBP-111/112
Use a screwdriver or fingernail to adjust the trimpot on the sensor housing to the desired time delay. Move the trimpot till it "clicks" into
the setting (5, 10, 15, 20, or 30 minutes).
Using the FSIR Remote - HBP-111 only
1. Aim the remote at the sensor.
2. Select New Settings and Adjust Time Delay.
3. Choose from the range of 1 min - 30 mins with 1 minute increments.
4. Select Send.
NOTE: Any adjustments made will override any previous settings whether manually made on the sensor or through the FSIR-100.
Surface mount
module
Remove nipple
Gasket
Nipple
IMPORTANT START-UP INFORMATION
ADJUSTMENTS
Light Level
Adjustment
Trimpot
Time Delay/
Motion Sensitivity
Adjustment
Trimpot
Red
Load
White
1. Determine the mounting location appropriate to the features of the
sensor and the coverage area. Careful consideration must be given
to sensor placement. Avoid placing the sensor where the edge of the
fixture, shelving or other obstructions may block the sensor's line of
sight. Mount the sensor below the edge of the fixture and away from
the fluorescent lamps so that the heat from the lamps does not affect
the sensor.
2. Make sure that you have the appropriate accessories for the sensor
mounting configuration. (See Mounting Options.)
3. Assemble any necessary mounting accessories and attach them to
the sensor, making sure that the flying leads from the power module
are accessible.
4. Connect the line voltage and load wires to the sensor leads as shown
in the Wiring Diagram for the unit's application.
• Do not allow bare wire to show.
• Make sure all connections are secure.
5. Restore power from the circuit breaker.
3
WIRING
Push Button
IR Transmitter
IR Receiver
PIR
Sensor
Detection
(do not
Indicator
touch)
LED
Black
Hot
Neutral
INSTALLATION

Publicité

Table des Matières
loading

Ce manuel est également adapté pour:

Wattstopper hbp-111Wattstopper hbp-112

Table des Matières