8. Dimensional drawings

4.6
57
24
Fig. 6. SINEAX 2I1
for wall mounting.

9. Application example

The output signal generated by the KINAX 3W2 is needed both for local and remote measurement.
Problem:
Is the burden R2 connected across the output signal of the isolating transformer type 84-2I1-10 sufficient for local measu-
rement? If not, then use, for example, SINEAX TV 808.
X
2-wire
transducer
e.g KINAX 3W2
mA
4...20 mA
Fig. 10. Typical circuit with an isolating transformer SINEAX 84-2I1-10, transmitter KINAX 3W2 for angular measurement and a power supply
unit SINEAX B 811.
14
74
Fig. 7. SINEAX 2I1
for mounting on G-type rail,
EN 50 035 – G32.
Burden R1
(assumption 50 Ω)
≥12 V
U
M
U
= U
E
= 11 V for R1 = 50 Ω
U
E
≤15V
U
E
DC signal
U
V
isolator
84-2I1-10
U
A
4...20 mA
Local
measurement
Burden R2
Fig. 8. SINEAX 2I1
for mounting on cap-type rail,
EN 50 022-35 × 7.5.
Power pack
e.g. SINEAX B 811
24 V U
S
– U
S
M
Power supply
= 3 V
69.5
Fig. 9. SINEAX 2I1
for mounting on
cap-type rail,
EN 50 045-15 × 5.5.
Burden R3
≤ 750 Ω
0...20 mA
U
= U
– U
– U
– (R1 · 20 mA) = 8 V
A
S
M
V
UA [V]
Burden R2 [Ω] =
0.02 [A]
69
Remote
measurement
= 400 Ω