Télécharger Imprimer la page

CARLO GAVAZZI PD30CTP/R BP IO Serie Manuel D'instructions page 33

Publicité

Les langues disponibles
  • FR

Les langues disponibles

  • FRANÇAIS, page 89
2.7. Diagnostic parameters
2.7.1. Operating hours
The sensor has a built-in counter that logs every hour in which the sensor has been operational. The actual
number of operating hours can be read through the SCTL55 or an IO-Link master.
2.7.2. Number of power cycles [cycles]
The sensor has a built-in counter that logs every time the sensor has been powered-up. The value is saved
every hour. The actual number of power cycles is recorded and can be read through the SCTL55 or an
IO-Link master.
2.7.3. Maximum temperature – all time high [°C]
The sensor has a built-in function that logs the highest temperature that the sensor has been exposed to during
its full operational lifetime. This parameter is updated once per hour and can be read through the SCTL55 or
an IO-Link master.
2.7.4. Minimum temperature – all time low [°C]
The sensor has a built-in function that logs the lowest temperature that the sensor has been exposed to during
its full operational lifetime. This parameter is updated once per hour and can be read through the SCTL55 or
an IO-Link master.
2.7.5. Maximum temperature since last power-up [°C]
From this parameter the user can get information about what the maximum registered temperature has been
since start-up. This value is not saved in the sensor, however it can be read through the SCTL55 or an IO-Link
master.
2.7.6. Minimum temperature since last power-up [°C]
From this parameter the user can get information about what the minimum registered temperature has been
since start-up. This value is not saved in the sensor, however it can be read through the SCTL55 or an IO-Link
master.
2.7.7. Current temperature [°C]
From this parameter the user can get information about the current temperature of the sensor. The Temperature
can be read through the SCTL55 or an IO-Link master.
2.7.8. Detection counter [cycles]
The sensor logs every time the SSC1 changes state. This parameter is updated once per hour and can be read
through the SCTL55 or an IO-Link master.
2.7.9. Minutes above maximum temperature [min]
The sensor logs how many minutes the sensor has been operational above the maximum temperature. The
maximum number of minutes to be recorded is 2 147 483 647. This parameter is updated once per hour and
can be read through the SCTL55 or an IO-Link master.
2.7.10. Minutes below minimum temperature [min]
The sensor logs how many minutes the sensor has been operational below the minimum temperature. The
maximum number of minutes to be recorded is 2 147 483 647. This parameter is updated once per hour and
can be read through the SCTL55 or an IO-Link master.
2.7.11. Download counter
The sensor logs how many times its parameters have been changed. The maximum number of changes to be
recorded is 65 536. This parameter is updated once per hour and can be read through the SCTL55 or an
IO-Link master.
33
Rev.01 - 08.2022 | MAN PD30CTP/R IO-Link ENG | © 2022 | CARLO GAVAZZI Industri

Publicité

loading