Electrical connection
(non-Canada) - 3 wire cord
3-wire receptacle
(NEMA type 10-30R)
WARNING
ELECTRICAL SHOCK HAZARD
Failure to disconnect power source before
servicing could result in personal injury or
even death.
1. Turn off power supply to outlet.
2. Remove the screw securing the terminal
block access cover on the back of the dryer.
3. Install a UL-approved strain relief according
to the power cord/strain relief manufac-
turer's instructions in the power cord entry
hole below the access panel. At this time,
the strain relief should be loosely in place.
4. Thread an UNPLUGGED, UL-approved, 30
amp. power cord, NEMA 10-30 type SRDT,
through the strain relief.
30 AMP
NEMA 10-30
5. Attach the power cord neutral (center wire)
conductor to the SILVER colored center
terminal on the terminal block. Tighten the
screw securely.
6. Attach the remaining two power cord outer
conductors to the outer, BRASS colored ter-
minals on the terminal block. Tighten both
screws securely.
INSTALLATION INSTRUCTIONS
DO NOT make a sharp bend or crimp wiring/
conductor at connections.
7. Follow manufacturer's guidelines for firmly
8. Reinstall the terminal block cover.
Neutral
(center wire)
If moving dryer from a 4-wire system and
installing it in a 3-wire system, move the
internal ground from the center terminal
back to the GREEN screw next to the
terminal block.
DO NOT remove
internal ground in
a 3-wire system!!
WARNING
ELECTRICAL SHOCK HAZARD
securing the strain relief and power cord.
IMPORTANT
Neutral
terminal
15