11.1. Insulation
To avoid dew drops, provide suffi cient anti-sweating insulation to
the refrigerant and drain pipes. When using commercially available
refrigerant pipes, be sure to cover with available insulating material
with heat-resistant temperature of more than 100 °C [212 °F] and
thickness given below, on both liquid and gas pipes. Insulate all
indoor pipes with polyethylene insulation with a minimum density of
0.03 and a thickness as specifi ed in the table below.
11.2. Piping size
Model
Refrigerant
Liquid pipe
pipe
Gas pipe
Drain Pipe
PVA-AA4
30-36-42
9.52 mm [3/8]
15.88 mm [5/8]
O.D. 32 mm [1-1/4]
Pipe size
6.4 mm to 25.4 mm [1/4 to 1 in.]
28.6 mm to 38.1 mm [1-1/8 to 1-1/2 in.]
-If the unit is used on the highest story of a building and under
high temperature and high humidity, it is necessary to use thicker
insulation than specifi ed in the table above
-If there are customer's specifi cations, please follow them.
Insulation thickness
>10 mm [7/16 in.]
>15 mm [5/8 in.]