saia-burgess ALE3D5FD10C3A00 Instructions De Montage Et D'exploitation page 4

Publicité

Les langues disponibles

Les langues disponibles

Assembly and operating instructions Type ALE3D5FD10
65 A Three-phase active power energy meter with Modbus interface, Pic. 1
Description
Energy meter with RS485 Modbus interface enables the
reading of all relevant data like meter reading, electricity,
voltage and power (active and reactive).
Technical data
Connection
Pic. 2
diagram
Dimensions
Pic. 3
Accuracy class
B, according to EN50470-3,
Cl. 1 according to IEC62053-21
Reference, Maxi-
I
= 10 A, Im
ref
mum, initial current
operating voltage
3 × 230/400 V
Tolerance -20%/+15%
Counting range
00000,00...999999,9 kWh
LED-Ouptut
1'000 Imp/kWh
(Only MID)
Connections
Conductor cross-section 1,5...16 mm
Main circuit
Screwdriver Pozi No. 1, slotted
No. 2, breakaway torque 1,5...2 Nm
Connections
Conductor cross-section max. 2,5 mm
Control circuit
Screwdriver Pozi No. 0, slotted
No. 2, breakaway torque 0,8 Nm
Operating
-25... +55°C (noncondensing
temperature
according standard EN50470)
Indicating elements
(Pic. 4)
Shows total consumption Tariff 1
T1total
Shows partial consumption for
T1part.
Tariff 1, this value is resettable
Shows total consumption Tariff 2
T2total
Shows partial consumption for
T2part.
Tariff 2, this value is resettable
Shows the instantaneous power
P(kW)
per phase or all phases
Shows the voltage per phase
U(V)
Shows the current per phase
I(A)
100 Imp/kWh (only
Pulsates according to drawn power
for Product without MID)
Shows the unit kWh when the
kWh
consumption is displayed
For P-, U-, I- or Error display, the
L1 / L2 / L3
corresponding phase is displayed
In case of missing phase or wrong
Error
current direction. The corresponding
phase is additionally displayed.
4 319 5113 0a
= 65 A, Ist
40 mA
ax
=
, 50 Hz
AC
11.2012
Notes before connecting
1. Do not connect L1, L2 or L3 to N
2. In order to avoid moisture in the meter due to
condensate build-up, acclimatise the meter at room
temperature for about half an hour before connecting.
3. N must always be connected.
Attention!
These devices must only be installed by a professional
electrician, otherwise there is the risk of fire or the risk
of an electric shock.
Operation of the LCD display
See page with LCD menu navigation
Installation instructions
The three-phase energy meter can be attached to a
,
2
35 mm rail (EN60715TH35).
The meter can be used only in installation cabinets.
,
2
Declaration of Conformity CE
We, Saia-Burgess Controls Ltd., CH 3280 Murten
(Switzerland),herewith declare, on our own responsibil-
ity that the products:
ALE3D5FD10C3A00
which this certificate refer to, are in accordance with
the following standards:
EN50470 parts 1 and 3 (electronic meter), of
October 2006.
Directive 2004/22/EG of the European
parliament and of the council regarding measuring
instruments
• Annex I, essential requirements
• Annex MI-003, active electrical energy meters
EC - Declaration of Conformity: 2010
Saia-Burgess Controls AG
Conformity Assessment Body:
Zertifizierungstelle METAS-Cert, Nr. 1259
CH-3003 Bern-Wabern
Signed:
Jean-Paul Costa, Head of development
Subject to change without notice