ENGLISH OPERATING INSTRUCTIONS
CONSIGNES D'UTILISATION
DX
DXN SERIES
©2023 MELTRIC Corporation. All rights reserved.
MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132
Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com
A manufacturer of products using Marechal technology
meltric.com
GENERAL
MELTRIC's DXN Series plugs & receptacles are
designed and rated for use in hazardous environments
where explosive gases or dusts may be present.
The DXN receptacle has a dead front, which isolates
the supply contacts and prevents user exposure to live
parts. The receptacle's safety shutter blocks access to
the contacts and can only be opened by DXN plugs
with compatible ratings and contact configurations.
WARNING
There are inherent dangers
associated with electrical
products. Failure to follow safety precautions can result in
DANGER
serious injury or death. These instructions must be
followed to ensure the safe and proper installation,
CAUTION
operation and maintenance of the MELTRIC devices.
Before installation, disconnect all sources of power to
the circuit to eliminate the risk of electrical shock.
NOTICE
RATINGS & CERTIFICATIONS
ADVERTENCIA
To ensure the safe use of this product, the
installer must verify that the product is properly
DANGER
rated for the application.
The amperage and voltage ratings are indicated on
CAUTION
the device labels. Some DXN devices are provided
WARNING
with optional auxiliary contacts that make after and
break before the phase contacts. The ratings for
AVISO
auxiliary contacts are shown in Table 1.
DANGER
Hazardous Duty Ratings
CAUTION
Table 1 - Auxiliary Contact Ratings
Device
120VAC 240VAC 480VAC
DXN30,60
5A*
5A*
NOTICE
DXN plugs & receptacles have both ATEX and CSA
ratings for use in hazardous environments.
ATEX – Class 1 Zone 1 AEx ed IIC T6
This rating certifies the product for use in surface
(non-underground) applications where a high level
of protection is required and where the presence of
an explosive atmosphere of any type of gas or dust
is likely to occur. The associated maximum surface
temperature of the product is 85°C (185°F), at an
ambient temperature of 40°C (104°F).
CSA – Class 1 Division 2 Group A, B, C, D
Class 2 Division 2 Group E, F, G
This rating certifies the product for use in applications
where flammable gases, such as acetylene, hydrogen,
ethylene or propane, or dusts, such as magnesium,
coal or grain, may be present under abnormal conditions.
INSTALLATION
DXN's must be used in conjunction with other
appropriately rated hazardous duty products
and must be installed by qualified electricians in
accordance with all applicable local and national
electrical codes.
WARNING
Before starting, ensure that the power is off and verify
that the conductors meet the requirements of the
National Electric Code and are within the capacities of
the DXN terminals noted in Table 2.
Table 2 - Wiring Terminal Capacity
INSDXN Q
NOTICE
DXN20
DXN30
DXN60
Capacity is based on certification testing. Wire size
1
should be determined in accordance with the electrical code.
Auxiliary contacts are optional
2
General Notes & Precautions
1.
Self-tapping screws are provided for use with
some polymeric accessories. High torque may
be required to drive them in and fully seat the
gasket/s. Once they are seated, care should be
taken in order to avoid over-tightening them against
the poly material. Poly Box with 70° Poly Angle
accessory: captive screws must be tightened to a
torque of 1.2Nm (10.62 in-lbs)
Metal Box with 70° Poly Angle accessory:
captive screws must be tightened to a torque
of 2.0Nm (17.7 in-lbs)
2.
Wire strip lengths are indicated in Table 3.
Strip lengths for cable sheathing will depend
on the specific application. When used with
handles, the cable sheathing should extend
into the handle to ensure secure cord gripping.
Table 3 - Wire Strip Length - A (receptacle/inlet)
DXN20 - Main
DXN30 - Main
DXN30 - Aux.
DXN60 - Main
DXN60 - Aux
3.
Wiring terminals are spring assisted to prevent
loosening due to wire strand settlement, vibration
& thermal cycling. They should not be over-tightened.
Appropriate tools and tightening torques are indicated
600VAC
in Table 4. NOTICE: Do not back terminal screws
5A*
5A* (550V max)
completely out.
Table 4 - Recommended Tightening Torques
Terminal
DXN20
DXN30
DXN30
DXN60
DXN60
Assembly for In-line Plugs/Connectors
Do not overtighten terminal or self-tapping
DANGER
CAUTION
1
Main Contacts
Aux. Contacts
Max
Min
Max
10
16
N/A
6
14
10
4
10
10
Inches
mm
0.50/0.50
12/12
0.79/0.83
20/ 21
0.67/0.67
17/ 17
0.79/0.83
20/21
0.67/0.83
17/21
Torque
Flat Screwdriver
7.1 in-lbs
1/8" precision tip
10.6 in-lbs
3/16" precision tip
(Main Contacts)
7.1 in-lbs
1/8" precision tip
(Aux. Contacts)
17.7 in-lbs
3/16" precision tip
(Main Contacts)
7.1 in-lbs
1/8" precision tip
(Aux. Contacts)
screws. Tighten screws to the proper torque to ensure
a secure connection.
Flexible cord connected devices must be equipped with
a flexible cord listed for extra hard usage and terminated
with listed fittings in accordance with all applicable
local and national electrical codes. See table 6.
Table 6 - Flexible Cord
Type
Extra Hard
Usage
DXN devices are rated to make and withstand short
circuit currents with appropriate fusing as indicated
in Table 5.
Table 5 - Short Circuit Make & Withstand Ratings
Device
DXN20 - 20A
DXN30 - 30A
- AWG
DXN60 - 60A
2
* DXN20, 30 Ratings are based on testing with Mersen
Non-Time delay current limiting fuses
DXN60 Ratings are based on testing with Little Fuse
Non-Time delay current limiting fuses
* Note: Consult NEC for short circuit limits
When DXN's are used as in-line connectors, finger
drawplates should be installed on both the receptacle
and plug in order to more easily provide the leverage
required to properly connect the devices.
Threaded
Bushing
Adapter
Strain
Relief
Handle
Compression
Nut
Loosely re-assemble the compression nut, bushing and
strain relief to the threaded adapter on the end of the
handle and insert the cable through it, the thin black
drawplate gasket and finger drawplate (if applicable),
and the color-coded gasket. Being mindful that the
strain relief must clamp on the cable sheath, strip the
cable sheath as required to provide a workable wire
length. Then strip the individual wires to the lengths
indicated in Table 3, and twist the strands of each
conductor together.
NOTICE: Back out the terminal screws on the receptacle
(or inlet) only far enough to allow the conductors to
pass, insert the conductors fully into their respective
terminals and tighten the terminal screws with a hand
screwdriver to the torque indicated in Table 4.
Verify that the cable jacket will extend beyond the
strain relief and into the handle.
receptacle (or inlet), the color-coded gasket, the
finger drawplate, and the thin black finger drawplate
gasket to the handle with the four self-tapping screws
provided. NOTICE: Over-tightening the screws may
cause cracking in polymeric components. Adjust the
cable location so that it will not be under tension inside
the handle and tighten the compression nut to secure
the cable.
Short Circuit MELTRIC's DXN Series Plugs &
Receptacles have short circuits make (close) and
withstand ratings up to 25kA when used with the
fusing shown in Table 5.
Assembly for Mounted Receptacles
(or Inlets)
In applications where DXN receptacles (or inlets) are
mounted to wall boxes, panels or other equipment,
optimal operation is achieved when the device
Flexible Cable Range
Max Nos of
Conductors
Max Øin
Min Øin
5
0.812
0.312
Rating Fuse
Type*
25 kA@600VAC
RK1
30A
25 kA@600VAC
RK1
70A
25 kA@600VAC
RK1
100A
Finger Drawplate Gasket
DXN20 Remove Adhesive Liner
Finger Drawplate
Color-Coded
Receptacle
Gasket
(or Inlet)
Assemble the

Publicité

loading

Sommaire des Matières pour Meltric DXN Serie

  • Page 1 Non-Time delay current limiting fuses DXN20 DXN60 Ratings are based on testing with Little Fuse Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com DXN30 Non-Time delay current limiting fuses A manufacturer of products using Marechal technology...
  • Page 2 Hole Pattern for Custom Mounting shown in figure 4. Close and latch the lid on the MELTRIC shall not be liable for any penalties or DXN20: 1.656" (42 mm) receptacle. consequential damages associated with the loss of DXN30: 1.890"...
  • Page 3 2 Usage 0.812 0.312 Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com pour les bornes DXN. Intense A manufacturer of products using Marechal technology Les produits de la série DXN sont fait pour supporter Tableau 2 –...
  • Page 4 Lorsque les prises DXN sont installées sur un boîtier à ce que la flèche rouge sur le boîtier de la fiche MELTRIC au travers du trou et mettre le cadenas mural, un panneau ou une pièce d'équipement, le soit alignée avec la flèche rouge qui se trouve ou autres dispositifs de cadenassage dans l’un des...
  • Page 5 MELTRIC Corporation / 4765 W. Oakwood Park Drive Franklin, WI 53132 Dispositivo Rango del Fusible Tipo* Tel. : 800 433 7642 / Fax : 414 433 2701 / e-mail : mail@meltric.com DXN60 DXN20 - 20 A 25 kA@600VCA 30 A...
  • Page 6 Montaje en Caja de Conexiones Para conectar una clavija y tomacorriente, primero presione de MELTRIC” en el barreno suministrado en el gatillo e el botón rojo en el gatillo para abrir la tapa del inserte el candado u otro dispositivo de bloqueo atraves En aplicaciones donde los dispositivos tomacorrientes tomacorriente, después oriente la clavija 1.

Ce manuel est également adapté pour:

Dxn20Dxn30Dxn60