Read the complete manual before attempting installation and activating the system.
1. DESCRIPTION
Galvanically isolated power supply (SELV) for DALI bus systems, DALI auxiliary power supply (specific Niko applica-
tion) or power supply for Silicon Controls control systems. Housing for DIN rail 4 modules, standard dimensions.
Adjustable output voltage of 22,5V or 16V, 225mA.
The Niko power supply provides an output voltage in SELV (safety extra low voltage). A DALI bus only operates
on ELV (extra low voltage: basic isolation of 2,5kV).
2. OPERATION
The 67-710 power supply provides a low voltage current of 22,5V or 16V. The standard output voltage is 22,5V.
If necessary, the voltage can be limited to 16V DC by means of a bridge between terminals 6 and 7. The current
is electronically limited to a max. of 240mA according to the DALI standard. The power supply is automatically
switched over to 16V DC voltage if a power supply is already connected to the bus with a voltage of less than
19V (tolerance 0,5 V DC).
A green LED (at the bottom between L and N) indicates the presence of the 230V power supply voltage. A red LED
(next to the 'protection' indication) indicates that the overcurrent or thermal safety device is operating.
3. INSTALLATION
Connect all terminals from 1 to 7 (4 and 5 unused) and L and N as shown in the table below.
Terminal n
.
Symbol
Function
o
1
V DC+
Low voltage power supply output +22,5V DC (SELV)
2
DALI+
Data connection DALI bus (ELV)
3
Common
Common (both for power supply and DALI bus)
4
Not used
5
Not used
6
Bridge
Power supply output on terminal limited to 1 max. +16V DC
7
Bridge
Power supply output on terminal limited to 1 max. +16V DC
L
Phase power supply input 230V~ 50Hz
N
Neutral conductor power supply input 230V~ 50Hz
3.1 Use as a DALI bus power supply
Only 1 power supply can be connected to the bus (max. 250mA current allowed on the DALI bus). First check
whether any other unit (e.g. a dimmer) is already providing the bus with power supply. The power supply is
connected to the bus by means of a bridge between terminals 1 and 2. Always make this connection on the
power supply, never on the circuit boards.
3.2 Use as an auxiliary power supply
Select the circuit boards that must be connected to the auxiliary power supply. (Procedure: see manual circuit
boards). Connect terminal 1 of the 67-710 to terminal 22,5V DC+ of each selected circuit board. Always make
this connection on the power supply and never on the circuit boards. Put the switch of the selected circuit
boards in the correct position.
3.3 Use as a Silicon Controls power supply
Connect the Silicon Controls power supply inputs to terminals 1 and 3.
ATTENTION!
Ballasts of different brands can be connected to the same bus. Controls of different brands CANNOT be connected
to the same bus just like that. Two parameters must be taken into account:
- Some manufacturers use non-standard control codes. It is therefore possible that the connected control system
will not work at all or only sporadically.
- Some control systems cannot handle the maximum voltage of the DALI bus (22.5V). It is therefore possible to
limit the power supply voltage of the 67-710 unit to max. 16V. Check the allowed power supply voltage of the
different control systems.
Table 1
Circuit board type
Power consumption circuit board and control points
Simple
2-fold
3-fold
4-fold
Table 2
Max. number of
Circuit board + control points
circuit boards
supplied via DALI bus (1)
Simple
2-fold
3-fold
4-fold
Table 3
Max. number of control points
Control points supplied via
Simple
2-fold
3-fold
4-fold
(1) Irrespective of whether the power supply is set to 22,5V or 16V.
(2) Can only be applied if used as auxiliary power supply (separate from DALI bus wiring). If the power supply
is connected via the DALI bus, only half of the power is available for the control systems. The other half is
reserved for the ECG.
- The DALI bus and auxiliary power supply can be connected separately in order to increase the number of control
points.
- The max. number of control points depends on the configuration. Every Niko circuit board uses 14mA. Every Niko
control point uses 2mA. The total consumption can be calculated by using table 1.
Consult Niko for further information.
14 + (1 x 2) = 16mA
14 + (2 x 2) = 18mA
14 + (3 x 2) = 20mA
14 + (4 x 2) = 22mA
Circuit board + control points sup-
plied via auxiliary power supply (2)
6
14
5
12
5
11
4
10
Control points supplied via
DALI bus (1)
auxiliary power supply (2)
6
10
15
16
- During normal operation, this power supply produces an amount of heat (max. 5W). Make sure this heat can
escape adequately. Do not cover the power supply with insulating materials. When mounting different devices in
the same enclosure, the temperature in the enclosure can exceed the ambient temperature. This can influence
the operation of the power supply (limitation of the max. capacity – thermal protection). Provide sufficient air
ventilation of the enclosure, so the temperature in the enclosure is always below 35°C.
- After a power cut, the power supply is automatically switched back on.
4. PRODUCT MAINTENANCE
- Regularly check whether the terminals are still firmly fixed.
5. TECHNICAL SPECIFICATIONS
- Operating voltage: 207 to 253V~, frequency 50Hz ±1%
- Circuit breaker: maximum MCB rating 6 A*
- Dimensions: 54,5 x 70 x 89mm
- DIN-rail mounting: to be mounted in a closed distribution board
- Weight: 0,400kg
- Ambient temperature during operation: min. 0°C, max. 35°C
- Non-condensing atmospheric humidity
- Stand-by power: 5W
- Max. ambient temperature: t a = 35°C
- Max. cable diameter per terminal: 2 x 2,5mm
- Max. load: 225mA
- Protection modes: thermal, overload and short-circuit protection
- Overload protection active from 240mA
- In conformity with the standard EN61558-1
- Information concerning galvanic isolation:
- SELV between connector terminals:
- 1 (VDC+) and 3 (common) except when connected to DALI bus (bridge between terminals 1 and 2)
- 6 and 7 (output voltage selection) except when connected to DALI bus (bridge between terminals 1 and 2)
- ELV between terminals:
- 1 (VDC+) and 3 (common) if bridge between terminals 1 and 2
- Connectors 6 and 7 are used to select the nominal output voltage:
- no bridge between terminals: 22,5V DC ±0,5V
- bridge between terminals: 16V DC ±0,5V
- Set power supply for Silicon Controls systems to 22,5V DC (no bridge)
- Niko circuit boards auxiliary power supply for DALI: 22,5V DC
- Niko circuit boards and control modules power supply: 22,5V DC
- power supply of DALI components from other manufacturers: depends on the technical specifications of
the manufacturer in question: if necessary 16V DC (place a bridge between terminals 6 and 7, bridge not
included)
- Compatible with DALI according to EN60929 (min. 7V DC max. 24V DC)
* The MCB rating is limited by national installation rules.
6. TROUBLESHOOTING:
Green LED off: no power supply (230V~ interrupted): check the connection, the position of the circuit breakers
and other protection devices.
Red LED lights:
- Either: bus overload: too many units connected to the DALI bus. Solution: switch over some of the circuit boards
to an auxiliary power supply by means of the switch provided (procedure: see circuit boards manual).
- Or: protection against over-heating. Check the temperature in the enclosure (max. 35° C) and, if necessary,
introduce measures for ventilation and/or cooling. The temperature protection is equipped with an auto-reset,
which will be activated as soon as the temperature has cooled down sufficiently.
- Or: protection against a short-circuit on the load side (e.g. short-circuit on the DALI bus). Check the various
connections. Switch the power supply after all short-circuits have been removed only.
Warnings regarding installation
The installation of products that will permanently be part of the electrical installation and which include dangerous
voltages, should be carried out by a qualified installer and in accordance with the applicable regulations. This
user manual must be presented to the user. It should be included in the electrical installation file and it should be
passed on to any new owners. Additional copies are available on the Niko website or via Niko customer services.
CE marking
This product complies with all of the relevant European guidelines and regulations. For radio equipment Niko llc
declares that the radio equipment in this manual conforms with the 2014/53/EU directive. The full text of the EU
declaration of conformity is available at www.niko.eu under the product reference, if applicable.
Environment
This product and/or the batteries provided cannot be disposed of in non-recyclable waste. Take your discarded
product to a recognised collection point. Just like producers and importers, you too play an important role in
the promotion of sorting, recycling and reuse of discarded electrical and electronic equipment. To finance the
rubbish collection and waste treatment, the government levies recycling charges in certain cases (included in
the price of this product).
Support & contact
14
24
nv Niko sa
Industriepark West 40
33
9100 Sint-Niklaas, Belgium
40
www.niko.eu
EN
+32 3 778 90 80
2
support@niko.eu
PM067-71000R23022

Publicité

loading