KAL740 Addressable Supervised Siren / Relay
Module Installation Sheet
EN ES
IT
PT FR NL CS NO PL HU
1
EN: Installation instructions
Description
The KAL740 provides a supervised relay output for sounders
or solenoid valves in an addressable fire detection system and
monitors the line they are connected to.
The module is used in detection systems that require an
auxiliary 24 VDC power supply.
Installation
Caution:
For general guidelines on system planning, design,
installation, commissioning, use and maintenance, refer to the
EN54:14 standard and local regulations.
© 2014 UTC Fire & Security. All rights reserved.
Module installation
Disconnect the fire system power supply and install the module
in the protective housing provided.
Connect the loop cable shield wire to the earth screw.
The 24 V power supply for the module must be provided by an
auxiliary power source.
Connection
The module connectors, DIP switch, and status LED are
shown in Figure 1:
1.
Earth screw
2.
Loop connectors
3.
Auxiliary power supply connectors
4.
Relay output connectors
5.
DIP switch
6.
Status LED
1 / 16
P/N 10-5151-501-105-01 • ISS 27NOV14

Publicité

loading

Sommaire des Matières pour Kilsen KAL740

  • Page 6 LED d’état Description La LED d’état est allumée en continu durant l’alarme. Le module KAL740 fournit une sortie de relais contrôlée pour sirènes ou valves à solénoïde dans un système de détection Maintenance et test d’incendie adressable et contrôle la ligne à laquelle elles sont La maintenance de base se limite à...
  • Page 13 P/N 10-5151-501-105-01 • ISS 27NOV14 13 / 16...
  • Page 14 14 / 16 P/N 10-5151-501-105-01 • ISS 27NOV14...
  • Page 15 P/N 10-5151-501-105-01 • ISS 27NOV14 15 / 16...
  • Page 16 16 / 16 P/N 10-5151-501-105-01 • ISS 27NOV14...