Télécharger Imprimer la page

ALERTON VIP-363-HOA Instructions D'installation page 2

Publicité

Les langues disponibles

Les langues disponibles

Installation
Mount devices in a position that allows clearance for wiring, servicing, removal, and terminal block connection.
The VIP controller and VXIO modules may be mounted in any orientation.
IMPORTANT Avoid mounting in areas where acid fumes or other deteriorating vapors can attack the metal parts of
the device, or in areas where escaping gas or other explosive vapors are present.
Power
The VIP controller and expansion modules require a 24 VAC [20 VAC (min), 30 VAC (max)], 50/60 Hz, half-wave
power from a UL Listed Class 2, 24 VAC transformer.
WARNING! Half-wave devices and full-wave devices must not use the same AC transformer. Maintain wiring polarity.
Fig. 1
Use separate transformers for controllers and load power.
Power Consumption
Total power consumption must be based on the sum of the VA rating for each controller and I/O expansion module. The
total must not exceed 100 VA. Figures 1 and 3 represent options for powering the I/O expansion modules separate
from the VIP-363-HOA controller.
VA Minimum
Load
Part
(No BO Load)
VIP-363-VAV
15 VA
VIP-363-HOA
15 VA
VXIO-322
6 VA
VXIO-965
3 VA
© Honeywell International Inc. All Rights Reserved
VA Maximum
BO Load
Load
(HOT A)
100 VA
100 VA
100 VA
100 VA
87 VA
72 VA
100 VA
100 VA
Printed in MEXICO
BO Load
BO 24 VAC
(HOT B)
Load Max
72 VA
1.5 A
72 VA
1.5 A
72 VA
1.5 A
72 VA
1.5 A
31-00254EF-05
06-22
Page 2

Publicité

loading

Produits Connexes pour ALERTON VIP-363-HOA

Ce manuel est également adapté pour:

Vip-363-vav