WHITE-RODGERS
Operator: Save these instructions for future use!
FAILURE TO READ AND FOLLOW ALL INSTRUCTIONS CAREFULLY
BEFORE INSTALLING OR OPERATING THIS CONTROL COULD CAUSE
PERSONAL INJURY AND/OR PROPERTY DAMAGE.
This sequencer is a direct replacement unit for sequenc-
ing both fan and heat. This sequencer has a solid-state
24 volt heater between the "H-H" terminals and a variety
of normally open contact sets. These contacts close and
open within specified timings and are used to control the
furnace fan and heating elements on demand from a
room thermostat.
THIS CONTROL MUST BE INSTALLED BY A QUALI-
FIED INSTALLER.
All wiring must conform to local and national electrical
codes and ordinances.
This control is a precision instrument, and should be
handled carefully. Rough handling or distorting compo-
nents could cause the control to malfunction.
This control has been accurately calibrated at the factory.
Any attempt to re-calibrate this control will void the White-
Rodgers warranty.
WARNING
!
Do not use on circuits exceeding specified volt-
ages. Higher voltages will damage control and
could cause shock or fire hazard.
If in doubt about whether your wiring is millivolt,
low or line voltage, have it inspected by a quali-
fied heating and air conditioning contractor or a
licensed electrician.
WHITE-RODGERS DIVISION
EMERSON ELECTRIC CO.
9797 REAVIS ROAD ST. LOUIS, MO 63123-5398
(314) 577-1300 FAX (314) 577-1517
All manuals and user guides at all-guides.com
Printed in U.S.A.
24A5X SERIES
Fan/Heat Sequencer
INSTALLATION INSTRUCTIONS
Some sequencers contain auxiliary contacts that are
used to energize the heater of another sequencer. This
arrangement provides a definite delay in energizing heat-
ing elements and prevents more than the required num-
ber of elements from being energized at the same time.
It also allows one room thermostat to control a large
number of elements without excessively high current
through the thermostat.
CAUTION
!
To prevent electrical shock and/or equipment
damage, disconnect electric power to system at
main fuse or circuit breaker box until installation
is complete.
Label all wires prior to disconnection when ser-
vicing controls. Wiring errors can cause improper
and dangerous operation.
Following installation or replacement, follow
appliance manufacturers' recommended instal-
lation/service instructions to insure proper op-
eration.
DESCRIPTION
PRECAUTIONS
PART NO. 37-3782B
Replaces 37-3782A
9715

Publicité

loading

Sommaire des Matières pour White-Rodgers 24A5X Serie

  • Page 1 If in doubt about whether your wiring is millivolt, low or line voltage, have it inspected by a quali- fied heating and air conditioning contractor or a licensed electrician. WHITE-RODGERS DIVISION Printed in U.S.A. PART NO. 37-3782B EMERSON ELECTRIC CO.
  • Page 2 All manuals and user guides at all-guides.com SPECIFICATIONS U.L. Ambient Rating: Auxiliary Switch - (Terminals designated “A”) -20° to +165°F (-29° to +74°C) 1.0A at 30 VAC non-inductive Terminals: Bimetal Heater - (terminals designated “H”) Dual 1/4" male quick-connect for combination Input: 24 VAC 60 Hz 0.16A AC Electrical Ratings: Main Switch - (Terminals designated “M”)
  • Page 3 Cette commande a été étalonnée avec précision à l’usine. ment peut causer un mauvais fonctionnement Toute tentative d’étalonnage de cette commande annule qui peut être dangereux. la garantie de White-Rodgers. Après l’installation ou le remplacement, suivre AVERTISSEMENT les instructions d’installation recommandées par le fabricant de l’appareil pour assurer le bon...
  • Page 4 All manuals and user guides at all-guides.com SPÉCIFICATIONS Conditions ambiantes selon U.L. : Commutateur auxiliaire - (bornes identifiées “A”) -29 à +74°C (-20 à +165°F) 1,0 A à 30 V CA non-inductif Bornes : Chauffage bi-métallique - (bornes identifiées “H”) Raccord rapide mâle double de 1/4"...
  • Page 5 Este control ha sido calibrado precisamente en la fábrica. errores en el cableado pueden producir una Toda acción para tratar de volverlo a calibrar anulará la operación incorrecta y peligrosa. garantía de White-Rodgers. Después de la instalación o del cambio, siga las ADVERTENCIA instrucciones de instalación/servicio recomen-...
  • Page 6 All manuals and user guides at all-guides.com ESPECIFICACIONES Clasificación del Ambiente de U.L.: Interruptor auxiliar - (Terminales designados “A”) -29° a +74°C (-20° a + 165°F) 1,0A a 30 VCA no inductiva Terminales: Calentador bimetálico - (Terminales designados “H”) Conexión rápida de 1/4" macho, doble, para Entrada: 24 VCA 60 Hz 0,16A combinación Capacidades eléctricas de CA:...