Test Run; Before Test Run - Mitsubishi Electric PUZ-A12 NHA7 Manuel D'installation

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

6. Electrical work
6.2. Field electrical wiring
Outdoor unit model
Outdoor unit power supply
Outdoor unit input capacity Main switch (Breaker) *1
Outdoor unit power supply
Indoor unit-Outdoor unit
Indoor unit-Outdoor unit earth
Remote controller-Indoor unit
Outdoor unit L1-L2 (single)
Indoor unit-Outdoor unit S1-S2 (single) *5
Indoor unit-Outdoor unit S2-S3 (single) *5
Remote controller-Indoor unit
*1. Be sure to ground the unit correctly. If required, take measures against leakage.
*2. Max. 50 m, 164 ft
S3 separated, Max. 80 m, 262 ft
*3. Max. 30 m, 100 ft
*4. The 10 m, 30 ft wire is attached in the remote controller accessory.
*5. The fi gures are NOT always against the ground.
S3 terminal has DC 24 V against S2 terminal. However between S3 and S1, these terminals are NOT electrically insulated by the transformer or other device.
Notes: 1. Wiring size must comply with the applicable local and national code.
2. Power supply cords, the Indoor-Outdoor connecting cable and the water heater-Outdoor connecting cable shall not be lighter than polychloroprene
sheathed fl exible cord. (Design 60245 IEC 57)
3. Use an earth wire which is longer than the other cords so that it will not become disconnected when tension is applied.
Warning:
In case of A-control wiring, there is high voltage potential on the S3 terminal caused by electrical circuit design that has no electrical insulation between power
line and communication signal line. Therefore, please turn off the main power supply when servicing. And do not touch the S1, S2, S3 terminals when the power
is energized. If isolator should be used between indoor unit and outdoor unit, please use 3-pole type.
Never splice the power cable or the indoor-outdoor connection cable, otherwise it may result in a smoke, a fi re or communication failure.

7. Test run

7.1. Before test run

After completing installation and the wiring and piping of the indoor and
outdoor units, check for refrigerant leakage, looseness in the power supply
or control wiring, wrong polarity, and no disconnection of one phase in the
supply.
Use a 500-volt megohmmeter to check that the resistance between the pow-
er supply terminals and ground is at least 1 MΩ.
Do not carry out this test on the control wiring (low voltage circuit) terminals.
Warning:
Do not use the air conditioner if the insulation resistance is less than 1 MΩ.
Insulation resistance
After installation or after the power source to the unit has been cut for an extended
period, the insulation resistance will drop below 1 MΩ due to refrigerant accumulat-
ing in the compressor. This is not a malfunction. Perform the following procedures.
1. Remove the wires from the compressor and measure the insulation resistance of
the compressor.
2. If the insulation resistance is below 1 MΩ, the compressor is faulty or the resist-
ance dropped due the accumulation of refrigerant in the compressor.
A12
A18
~/N (single), 60Hz,
~/N (single), 60Hz,
208/230 V
208/230 V
15 A
15 A
2 x Min. AWG 14
2 × Min. AWG 14
*2
3 x AWG 14 (polar)
3 x AWG 14 (polar)
*2 1 x Min. AWG 14 (polar) 1 x Min. AWG 14 (polar) 1 x Min. AWG 14 (polar) 1 x Min. AWG 14 (polar) 1 x Min. AWG 14 (polar) 1 x Min. AWG 14 (polar)
*4 2 × AWG 22 (Non-polar) 2 x AWG 22 (Non-polar) 2 x AWG 22 (Non-polar) 2 x AWG 22 (Non-polar) 2 x AWG 22 (Non-polar) 2 x AWG 22 (Non-polar)
*5
208/230 V AC
208/230 V AC
208/230 V AC
208/230 V AC
24 V DC
24 V DC
*5
12 V DC
12 V DC
208/230V
Single phase
Isolator
S1
A-Control
S2
Outdoor Unit
S3
A24
A30
~/N (single), 60Hz,
~/N (single), 60Hz,
208/230 V
208/230 V
25 A
25 A
2 × Min. AWG 12
2 × Min. AWG 12
3 x AWG 14 (polar)
3 x AWG 14 (polar)
208/230 V AC
208/230 V AC
208/230 V AC
208/230 V AC
24 V DC
24 V DC
12 V DC
12 V DC
3 poles isolator
S1
S2
S3
3. After connecting the wires to the compressor, the compressor will start to warm
up after power is supplied. After supplying power for the times indicated below,
measure the insulation resistance again.
• The insulation resistance drops due to accumulation of refrigerant in the com-
pressor. The resistance will rise above 1 MΩ after the compressor is warmed up
for 12 hours.
(The time necessary to warm up the compressor varies according to atmos-
pheric conditions and refrigerant accumulation.)
• To operate the compressor with refrigerant accumulated in the compressor, the
compressor must be warmed up at least 12 hours to prevent breakdown.
4. If the insulation resistance rises above 1 MΩ, the compressor is not faulty.
Caution:
• The compressor will not operate unless the power supply phase connection
is correct.
• Turn on the power at least 12 hours before starting operation.
- Starting operation immediately after turning on the main power switch can result
in severe damage to internal parts. Keep the power switch turned on during the
operational season.
A36
A42
~/N (single), 60Hz,
~/N (single), 60Hz,
208/230 V
208/230 V
30 A
30 A
2 × Min. AWG 10
2 × Min. AWG 10
3 x AWG 14 (polar)
3 x AWG 14 (polar)
208/230 V AC
208/230 V AC
208/230 V AC
208/230 V AC
24 V DC
24 V DC
12 V DC
12 V DC
A-Control
Indoor Unit
9

Publicité

Chapitres

Table des Matières
loading

Table des Matières