Triac controller for proportional control
of electric heating
EVR is a complete proportional controller for electric heating. It has
automatic voltage adjustment and can be used with either a built-in
sensor or an external sensor. EVR pulses the whole load On - Off.
The ratio between On-time and Off-time is varied 0 - 100% to suit the
prevailing heat demand. The current is always switched at zero
phase angle to prevent RFI.
EVR is only intended for control of electric heating: its con-
trol principle makes it unsuitable for control of motors or lighting.
EVR cannot control 3-phase loads, as one phase is regulated.
Technical data
Supply voltage:
200...415 V AC, 50...60 Hz, 1- or 2-phase,
with automatic voltage adjustment.
Power output:
Up to 16A, min. 1 A.
At 230 V, max. = 3.6 kW, min. = 230 W.
At 400 V, max. = 6.4 kW, min. = 400 W.
Max. 30°C (Note: EVR generates 20 W
Ambient temperature:
heating at full load.)
Storage temperature:
-40...+50°C.
P-band:
20 K (rapid temperature changes),
1.5 K (slow temperature changes)
I-time:
6 min (rapid temperature changes).
Pulse period:
60 s.
Red LED on EVR, lights up as power is
Indicator:
pulsed to the heater.
Surface, Wall.
Mounting:
Protection class:
IP20.
Supply air control: PI function using P-band
Control unit parameters:
20 K and I-time 6 min. Room control: P func-
tion using P-band 1.5 K.
Built-in sensor:
Measurement range 0...30°C.
For Energotech brand NTC sensors and
Input external
sensor/ setpoint:
setpoint devices, temperature range depends
on measurement range of sensor.
Weight:
0.3 kg.
Dimensions (HxBxD):
153 x 93 x 40 cm.
Settings
Setpoint:
0...30°C.
Night set-back:
0...10 K.
Control principle
EVR pulses the full load On-Off. EVR adjusts its mean power output to
the prevailing power demand by proportionally adjusting the ratio between
On-time and Off-time. The pulse period (= the sum of On-time and Off-
time) is fixed 60 seconds.
EVR has zero phase-angle firing to eliminate RFI.
EVR automatically adjusts its control mode to suit the control object
dynamics.
For rapid temperature changes (i. e. supply air control), EVR will act as a
PI controller with a proportional band of 20K and a reset time of 6
minutes.
For slow temperature changes (i. e. room control), EVR will act as a P
controller with a proportional band of 1.5K.
EVR
Assembly
Remove the front (the locking screw is located behind the setpoint
knob) and mount EVR vertically, so that the cooling flange is at its top.
Screws with a maximum head diameter of 5.5 mm can be used. If
EVR is to be used with the internal sensor, mount it approx. 1.5m
above floor level at a location with a representative temperature. The
air must be able to circulate freely around the EVR, without
disturbances from doors, furniture, etc.
If EVR is to be used with an external sensor it may be placed in any
location.
EVR emits approx. 20W of heat which must be dissipated. At
full load, the maximum ambient temperature is 30°C.
Electrical installation
The installation, which should be proceeded by a fully isolating switch
with a contact gap of at least 3 mm, should be carried out by a quali-
fied technician and in accordance with applicable directives.
K 1 2 U 3 4 U K G G
Figure 1: Wiring of supply voltage and heater
Terminals 1 and 2:
Not polarity sensitive.
Supply voltage:
200 - 415V AC, 50 - 60 Hz with automatic
voltage adjustment.
Maximum current:
16A.
Terminals 3 and 4:
Resistive single- or two-phase heater
Maximum load:
3680W at 230V (16A)
6400W at 400V (16A)
Minimum load:
230W at 230V (1A)
400W at 400V (1A)
CAUTION: The cooling flange is live!
1

Publicité

Table des Matières
loading

Sommaire des Matières pour Energotech EVR

  • Page 1 EVR, without Max. 30°C (Note: EVR generates 20 W Ambient temperature: disturbances from doors, furniture, etc. If EVR is to be used with an external sensor it may be placed in any heating at full load.) Storage temperature: -40...+50°C.
  • Page 2 Note: When using an external sensor, the equivalent sensor func- Replace the knob and check the result. Make fine adjustments if tion in the EVR must be disabled. This is done by setting the DIP- necessary. TG-K3xx switches to the right of the terminal strip according to figure 3.
  • Page 3 0...10 K. leave the switches in their downwards position. Switch on the Triac-regulator för steglös styrning av elvärme power again. EVR should not give out any power at all and the Reglerprincip LED should be extinguished. Check with a clamp-on amme-ter EVR pulsar hela den tillkopplade effekten Till-Från.
  • Page 4 OBS: Vid drift med extern givare måste motsvarande funktion kop- VARNING: Var försiktig vid arbete i EVR! Samtliga TG-G1xx plas bort i EVR. Detta görs genom att ställa skjutomkopplarna till komponenter, inklusive kylflänsen, är spänningsförande. höger om plintraden i enlighet med i figur 3.
  • Page 5: Régulateur Par Triac Pour Contrôle Proportionnel De Batterie Électrique De Chauffage

    La commutation de puissance s’effectue toujours au lysa. Kontrollera med tångamperemeter att ström går ut till info@energotech.se point 0 sur l’alternance et évite ainsi les perturbations. Le EVR est värmaren. www.energotech.se seulement conçu pour la régulation de batterie électrique de Om lysdioden är släckt och ingen ström går ut: Kontrollera...
  • Page 6: Principe De Regulation

    Fig. 2: Emplacement des switchs pour consigne et sonde interne. refroidissement vers le haut. Utiliser des vis avec un diamètre de tête TG-K3xx TBI-xx maxi de 5.5 mm. Si le EVR est utilisé avec la sonde interne, il est Bornes G et G: Pas de polarité. TG-G1xx nécessaire de le monter à...
  • Page 7: Normes De Compatibilité Électromagnétique

    Resserrer la vis de blocage en faisant attention à ne pas déplacer les Si la LED est éteinte mais que la batterie est alimentée, le EVR est bagues. Replacer le bouton et vérifier le résultat. Ajuster le réglage si fautif.
  • Page 8 Höchststrom: 16 A die Steuerung von Elektrowärme vorgesehen. Aufgrund des Regler- fast 60 s. EVR paßt die Reglermethode au-tomatisch an die Dynamik des Klemme 3 und 4: Resistive Ein- oder Zweiphasen-Heizung prinzips kann er nicht für die Motor- oder Beleuchtungssteu-erung Reglerobjekts an.
  • Page 9: Bei Einer Störung

    Der Bereich der Sollwerteinstellung kann mit Hilfe der Begrenzungs-ringe die Fühleranschlüsse G-G geöffnet lassen. Versorgungsspan- hinter dem Sollwertknopf mekanisch begrenzt werden. nung einschalten. Der EVR soll seine volle Leistung abgeben und die Leucht-diode Stellen Sie den Knopf auf einen Temperaturwert innerhalb des TG-K330 TG-R430 gewünchten Bereiches.
  • Page 10 Fühlerumschalter in ihrer untersten Stellung befinden. Ist kein Fehler festzustellen, liegt die Störung wah- rscheinlich im EVR. Wenn bisher kein Fehler gefunden wurde, sind der EVR und Fühler einwandfrei. Versorgungsspannung ausschalten, Kurzschlußbügel von den Eingängen G-G entfernen und evtl. einen externen Geber und/ oder Sollwertpotentiometer anschließen.

Table des Matières