Approvals
Udgangssignal / Output signal/
Ausgangssignal / Signal de
ATEX
Må med brandbare kølemidler kun anvendes i ex Zone 2 og i ikke klassificerede ex zoner.
Can only be used with flammable refrigerants in hazard Zone 2 or in non-classified hazardous zones.
Kann mit brennbaren Kältemitteln nur in der Ex-Zone 2, oder in nicht klassifizierten Ex-Zonen verwendet warden.
Peut être utilisé avec des fluides frigorigènes inflammables dans la zone dangereuse 2 ou non classes zones
dangereusesses, seulement.
Alle elektriske tilslutninger skal udføres iht. ATEX Zone 2 regulativet - samt EN 60079-14.
All electrical connections must comply with ATEX requirements for Zone 2 - and EN 60079-14.
Alle elektrischen Anschlüsse müssen gemäß ATEX Zone 2 Regeln und EN 60079-14 durchgeführt werden.
Tous les raccordements électriques doivent être effectués conformément aux régles ATEX zone 2.
Stikket må ikke fjernes, når sensoren er aktiveret.
Plug must not be removed when sensor is energized.
Stecker darf nicht entfernt werden, wenn der Sensor
aktiviert ist.
Le connecteur ne doit pas être retiré lorsque le capteur est
encore sous tension.
Ved anvendelser i ATEX Zone 2 områder ved temperaturer <-10 °C skal kabel og stik beskyttes mod slag.
When used in ATEX Zone 2 areas at temperatures <-10 °C the cable and plug must be protected against impact.
Wenn i ATEX Zone 2 bei Temperaturen <-10 °C verwendet werden, müssen die Kabel und Stecker gegen Stöße geschütz
werden.
Lorqu'ils sont utilisés en zone 2 ATEX à des températures <-10 °C, le câble et le connecteur doivent être protégés contre les
chocs.
2
sortie
AKS 32, 3000, 3050, 4050
4 – 20 mA
10 – 90%
1 – 5 V
1 – 6 V
0 – 10 V
European approvals:
According to EMC Directive 89/366/EEC.
American approvals: Must be powered by Class 2 power supply.
1. Temperature indicating and regulating equipment acc. to UL 873, file no E31024 and E311982.
2. Class I, Div. 2, Group A,B,C and D acc. to ANSI/ISA 12.12.01, file no E227388. MWP 75 bar/1088 bar.
Temperature code T4. AKS 32R/AKS 2050 85 °C (T4) or 105 °C (T3C) or 125 °C (T3B).
Australian approvals:
According to N1297.
Canadian approvals: Must be powered by Class 2 power supply.
1. Process control equipment acc. to CSA std. C22.2 no. 142-M1987.
2. Non-incendive electrial equipment for use in class I, Division 2, Group A, B, C and D acc. to
CSA std. no. C22.2 no. 213-M1987. MWP 75 bar/1088 bar. Temperature code T4.
IC.PI.P21.B2.52 / 520B6810
Bemærk / Note / Achtung / Attention
AKS 2050, 3050 & 4050 er udstyret med en dæmpedyse
AKS 2050, 3050 & 4050 are equipped with a damping orifice
AKS 2050, 3050 & 4050 ist mit einer Dämpfdüse ausgestattet
AKS 2050, 3050 & 4050: ce modèle est doté d'un orifice amortisseur
Forsyningsspænding / Supply voltage / Versorgungsspannung /
Tension d'alimentation [UB]
AKS 32R, 2050
nom. 5 V d.c.
9 – 30 V d.c.
9 – 30 V d.c.
15 – 30 V d.c.
AKS 33, 3000, 3050
10 – 30 V d.c.
EN60079-0; EN60079-15
Kabelet må ikke udsættet for nogen mekaniske
skader, korrosion, vibration, varme eller UV
stråling.
Cable must neither be exposed for any
mechanical damage, corrosion, vibration, heat
nor UV radiation.
Kabel müssen weder auf mechanische
Beschäcigungen, Korrosion, Vibration, Hitze
noch UV-Strahlung ausgesetzt werden.
Le câble ne doit être exposé à aucun
dommage mécaniques, à la corrosion, àux
vibrations, à la chaleur où aux radiations UV.