ME UNIQ
resetting
• M otorised resetting
1. Switch off the power supply to the motor (ME) connection for at least 5 sec.
2. Power the ME motor (respect the prescribed voltage) for at least 45 sec.
3. The resetting stops automatically when the end of range is reached (damper open).
• M anual resetting
1. Open the battery compartment (4) and press a 9V battery against the contact springs. Hold this position until the LED (3) stops flickering.
2. Control whether the indicator (2) indicates that the damper blade is open :
3. Remove the battery and close the battery compartment
Caution:
i
Meaning of the LED (3)
- If the LED flickers fast (3x/sec.), the battery is discharged: please use a new battery.
- If the LED flickers slowly (1x/sec.), the resetting is in progress.
- After the reset, the LED reflects the status of the magnet: Magnet powered = LED lit;
no power supply to magnet
i
Electrical connection:
- The connection must be compliant with NF S 61-932.
- When connecting the cables, it is necessary to use the cable-ties, as shown in the drawing included in the bag containing the cable-ties.
- After operation, the end-of-range switches (FDCU and FDCB) need 1 second to take a stable position.
r
/m
PcB
emove
ount the
1. remove the 2 screws
and open the lid.
If the product is manipulated in any other way than described in this manual, rf-technologies
will decline any responsibility and the guarantee will immediately expire!
Resetting-PCB
4
3
= LED off
2. remove the old PCB if
present.
3. Insert the new PCB and
fasten it with the screw.
5''
75''
+
4. Connect the PCB ME
UNIQ with the main PCB
of the UNIQ mechanism.
5. Connect the mechanism
according to the wiring
diagram and NF S 61-932.
K138-A
12/2016
6. Close the lid and fasten
with both sctrews.
7