All manuals and user guides at all-guides.com Inhalt Seite Content Page Contenu Page Anwendung Sicherheitsbestimmungen Montageanleitung Inbetriebnahme Fehlersuche Technische Daten Application Safety regulations Assembly instructions Starting up Troubleshooting Technical date Application Mesures de sécurité Instructions de montage Mise en service Recherche Caractéristiques techniques...
All manuals and user guides at all-guides.com HCC-11 Heizstrom- und Heizkreisüberwachungsmodul Anwendung Das Heizkreisüberwachungsmodul HCC-11 dient der Überwachung von Stromkreisen im Bereich von 1,25...40A, die mit Halbleiterrelais (SSR) geschaltet werden. Insbesondere ist das HCC-11 zur Überwachung von Heizkreisen mit mehreren Heizelementen (Heiznestern) geeignet. Der Ausfall eines Heizelementes wird zuverlässig überwacht.
All manuals and user guides at all-guides.com Montageanleitung: Montagezeichnung Die Montage des HCC-11 erfolgt auf das bereits montierte Halb- leiterrelais. Der Gehäusedeckel ist durch leichtes Auseinander- biegen seitlichen Halte- klammern zu lösen. Mit den bei- gefügten Schraubensätzen wird das Modul auf das SSR montiert elektrische Lastver- bindung hergestellt.
All manuals and user guides at all-guides.com Schalter 4 - Überwachung des maximalen Stromwertes Bei Verbrauchern mit erhöhtem Einschaltstrom, z.B. IR-Strahlern und Glühlampen, ist die Maximal-Stromüberwachung außer Betrieb zu setzen - Schalter 4 = ON Schalter 5 - Selbsthaltung von Störmeldungen Soll ein automatischer Reset der Störmeldung verhindert werden, so ist Schalter 5 in Stellung ON zu bringen.
All manuals and user guides at all-guides.com HCC-11 Heating current and circuit monitoring module Application The heating circuit monitoring module HCC-11 is designed to monitor electric circuits in the range 1.25A to 40A which are switched by solid-state relays (SSR). The HCC-11 system is primarily intended for monitoring heating circuits and also for detecting and localizing faults in single heating elements.
All manuals and user guides at all-guides.com Assembly drawing Assembly instructions The HCC-11 is mounted on the solid-state relay, which already installed. The housing cover is to be released by slightly bending apart the lateral retaining clips. The module is mounted on the solid-state relay electric load...
All manuals and user guides at all-guides.com Switch 4 - Monitoring of the maximum current value When using loads with a high inrush current, e.g. infra-red heaters and light bulbs, the maximum current monitoring should be switched off (setting: Sw4 = ON). Switch 5 - Self-holding of malfunction alarm If an automatic reset of the malfunction alarm is not desired, then Sw5 should be set to ON.
All manuals and user guides at all-guides.com Technical data Auxiliary supply: DC 24V ± 25% (integral polarity reversal protection) AC 24V ± 20% Current input: Typically 25 mA (without alarm load) Mains frequency (for load): 50/60 Hz Current ranges: prescalation with DIP switch 1.25A to 5A;...
All manuals and user guides at all-guides.com Module de surveillance du courant et du circuit de chauffage HCC-11 Application Le module de surveillance du circuit de chauffe HCC-11 permet de contrôler des circuits électriques commutés par des relais à semi-conducteurs (SSR = Solid State Relay) sur une plage de 1,25...40 A. Le module HCC-11 est particulièrement adapté...
All manuals and user guides at all-guides.com Instructions de Dessin de montage montage : Le montage du module HCC-11 s’effectue sur le relais à semi- conducteurs préalablement ins- tallé. Le couvercle du boîtier se démonte par une légère flexion vers l’extérieur des étriers de retenue latéraux.
All manuals and user guides at all-guides.com Commutateur 5 – auto-entretien d'alarmes Lorsqu’une réinitialisation automatique de l'alarme doit être inhibée, positionner le commutateur 5 sur ON. Une alarme qui survient ne peut être mise à zéro que par désactivation de la tension de service.
All manuals and user guides at all-guides.com Caractéristiques techniques Tension de service : C.C. 24 V ± 25% (détrompeur intégré) C.A. 24 V ± 20% Consommation de courant : Typ. 25 mA (sans charge d'alarme) Fréquence du secteur pour circuit de 50/60 Hz charge : Plages de mesure du courant :...