Trac-Master Two-Circuit Current Limiting End Feed/In-Line Feed Connector
Read and understand these instructions before installing fixture.
This fixture is intended for installation in accordance with the National Electrical Code and local regulations. To
assure full compliance with local codes and regulations, check with your local electrical inspector before installation.
To prevent electrical shock, turn off electricity at main circuit breaker panel before proceeding.
SAVE THESE INSTRUCTIONS
Current Limiting End Feed/In-Line
Feed Connector TUCLF11 and
TUCLF21 for use with Trac-Master
Two-Circuit Trac only. Current
Limiter will limit the wattage on
a circuit and can be used as a
standard ON/OFF switch.
Current limiting feed can be fed using a
4" octagon junction box, fed directly using
flexible or rigid conduit with 3/8" or 1/2"
electrical connector from standard ceilings
or grid ceiling runner systems, or fed using
Trac Pendant Mounting Kits.
NOTE:
1. Turn off power at breaker box before
installing electrical connector and trac.
2. If feeding with electrical connectors do
not use feed connector as a conduit
support. Independent conduit supports
must be used to attach the conduit to the
building structure.
3. Observe polarity; white neutral wire must
be connected to the terminal marked "N" in
the feed connector.
4. Use 12 gauge or 14 gauge solid wire in
feed connector only. Feed connector rating
120V, 20Amp max., 60Hz.
5. Use the proper rated Juno current limiting
circuit breaker (TCL Series) to limit the
load on the circuit (current limiting circuit
breaker sold separately).
6. Feed connector is polarized and will only
install into one end of the trac. Align
polarity arrow on feed connector toward
trac polarity line for proper installation.
See Figure 1.
7. Do not position luminaire such that it
touches the feed connector.
Note: This Current Limiting Trac Feed
Connector conforms to ASHRAE 90.1
Section 9.1.4(c) and is certified to California
Energy Commission T24-2008, Section
119(L) of the California Energy Code.
1300 South Wolf Road • Des Plaines, IL 60018 • Phone 800-323-5068 • www.junolightinggroup.com
INSTALLATION INSTRUCTIONS
For TUCLF11 and TUCLF21
INSTALLING CURRENT LIMITING
FEED CONNECTOR ON A J-BOX
The centerline of the trac must be on the
center of the J-Box and the mounting holes
for the J-Box must be at a 45º angle to the
centerline of the trac.
1. Remove the COVER and retain.
2. Remove the RECTANGULAR KNOCK
OUT from the PLATE. Do not remove any
other knock outs.
3. Push CURRENT LIMITING CIRCUIT
BREAKER(S) into PLATE.
4. Fasten PLATE to J-Box passing supply
wires through RECTANGULAR HOLE.
Secure PLATE by passing (2) Mounting
screws (not supplied) through PLATE and
into J-BOX.
5. Attach wires per WIRING INSTRUCTIONS
on page 2.
6. Slide TRAC onto FEED CONNECTOR;
ensure (2) CONTACT BLADES
insert into the gap of the trac BUS BARS.
7. Tighten FEED CONNECTOR ONE-WAY
LOCKING SCREW(S) for permanent
mounting to the trac (in accordance with
CEC-T24-2008.)
8. Apply VA label provided loose with circuit
breaker packaging onto the mounting
plate according to each trac VA rating (in
accordance with CEC-T24-2008.)
9. Fasten COVER taking caution to avoid
pinching any wires.
See OPERATING INSTRUCTIONS on page 2.
INSTALLING CURRENT LIMITING
FEED CONNECTOR USING
FLEXIBLE OR RIGID CONDUIT
1. Remove the COVER and retain.
Figure 1
© 2009 Juno Lighting LLC
2. Mark centerline of PLATE on ceiling to
determine the mounting location of the
FEED CONNECTOR.
3. Make a hole in the ceiling for the electrical
connector in the position that coincides
with one of the ROUND KNOCK OUTS.
4. Remove one ROUND KNOCK OUT
where the power is to be passed through.
Do not remove any other knock outs.
5. Push CURRENT LIMITING CIRCUIT
BREAKER(S) into PLATE.
6. Attach electrical connector (by others) to
PLATE in round hole.
7. Pass supply wires through hole in ceiling
and through electrical connector.
8. Mount PLATE to ceiling using (2) of the
PLATE MOUNTING HOLES that are not
located on a knock out. Mounting hardware
not supplied.
9. Attach wires per WIRING INSTRUCTIONS
on page 2.
10. Slide TRAC onto FEED CONNECTOR;
ensure (2) CONTACT BLADES insert
into the gap of the trac BUS BARS.
11. Tighten FEED CONNECTOR LOCKING
SCREW(S).
12. Fasten COVER taking caution to avoid
pinching any wires.
See OPERATING INSTRUCTIONS on page 2.
INSTALLING CURRENT LIMITING
FEED CONNECTOR ON
PENDANT MOUNTED TRAC
1. Follow instructions included with the
pendant mounting kits.
2. Install CURRENT LIMITING CIRCUIT
BREAKER(S) into PLATE.
3. Attach wires per WIRING INSTRUCTIONS
on page 2.
4. Slide TRAC onto FEED CONNECTOR
ensure (2) CONTACT BLADES insert into
the gap of the trac BUS BARS.
5. Tighten FEED CONNECTOR LOCKING
SCREW(S).
6. Fasten COVER taking caution to avoid
pinching any wires.
See OPERATING INSTRUCTIONS on page 2.
Printed in USA
Rev 5/09
P2473
pg 1 of 2

Publicité

loading

Sommaire des Matières pour JUNO TUCLF11

  • Page 1 INSTALLING CURRENT LIMITING 120V, 20Amp max., 60Hz. 9. Fasten COVER taking caution to avoid FEED CONNECTOR ON 5. Use the proper rated Juno current limiting pinching any wires. PENDANT MOUNTED TRAC circuit breaker (TCL Series) to limit the See OPERATING INSTRUCTIONS on page 2.
  • Page 2: Installation Instructions

    Juno Lighting Group’s factory after prior written return authorization has been granted. This warranty shall not apply to products which have been altered or repaired outside of Juno Lighting Group’s factory. This warranty is in lieu of all other warranties, expressed or implied, and without limiting the generality of the foregoing phrase, excludes any implied warranty of merchantability.
  • Page 3 DE CORRIENTE UTILIZANDO Conector de fuente en un extremo/en la INSTALACIÓN DEL CONECTOR CONDUCTO FLEXIBLE O RÍGIDO línea del limitador de corriente TUCLF11 PARA FUENTE CON LIMITADOR 1. Retire la TAPA y sujete. y TUCLF21 para utilizar sólo con riel DE CORRIENTE EN UNA CAJA 2.
  • Page 4 Juno Lighting Group garantiza que sus productos están libres de defectos de material o mano de obra. La obligación de Juno Lighting Group se limita expresamente a la reparación o el reemplazo sin cargo, en la fábrica de Juno Lighting Group, previo otorgamiento de una autorización de devolución por escrito.
  • Page 5: Mode De Montage

    D’ALIMENTATION À LIMITATION DE COURANT À L’AIDE D’UNE CANALISATION SOUPLE OU Connecteur d’alimentation en ligne/en MONTAGE D’UN CONNECTEUR bout limiteur de courant TUCLF11 et D’ALIMENTATION LIMITEUR DE RIGIDE TUCLF21 pour le rail à circuit double COURANT SUR UNE BOÎTE DE 1.
  • Page 6: Le Connecteur D'alimentation En Ligne/En Bout Limiteur De Courant À Circuit Double Trac-Master

    GARANTIE Juno Lighting Group garantit que ses produits sont exempts de défauts de matière et de façon. L’obligation de Juno Lighting Group se limite expressément à la réparation ou au remplacement, à titre gratuit, à l’usine de Juno Lighting Group après qu’une autorisation écrite de retour ait été...