3.3

Stopping the dryer

a) Use the switch to stop the dryer.
b) Stop the dryer 2 minutes after shutting down the air compressor or interrupting
the air flow to the dryer.
Avoid allowing compressed air to enter the dryer when the dryer is
switched off or when it is in an alarm situation which stops the refrigeration
compressor.
3.4

Operation

S The dryer operates automatically. It is factory set for a dew point of 37˚F (3˚C)
(ISO 7183, Part 2) and therefore requires no further calibration.
S Do not exceed the machine's design limits, bypass excess air flow and check the
unit model and/or installation.
S For maximum performance from your dryer, follow the maintenance schedule de-
scribed in Chapter 4.
S The sound pressure level recorded for these dryers 40 inch (at 1 metre) from the
machine in free field conditions is less then 50 dB(A) (models SR- - 5 --- SR- - 15),
55 dB(A) (models SR- - 25 --- SR- - 100)
Fig. 5 shows the Dryer's refrigeration and air circuits.

4 Maintenance

Before accessing live electrical parts
dryer using disconnect switch QS or disconnect the cable connections.
SAFETY DEVICES
SK overload protector
HP high pressure switch (installed on models SR- - 50 --- SR- - 100)
COMPRESSOR TYPE
HERMETIC, PISTON (single phase)
N.B.: Always use original spares supplied by the manufacturer.
Failure to do so renders the manufacturer not liable for incorrect unit operation.
4.1

Preventive maintenance

For optimum performance from your dryer follow the periodic maintenance sched-
ule described below.
CONDENATE DRAIN
CONDENATE DRAIN
WEEKLY
WEEKLY
Verify that the condensate drain is draining correctly.
COMPRESSOR
MONTHLY
MONTHLY
Make sure the compressor head temperature is below 140 F (60 C)
Make sure the compressor head temperature is below 140˚F (60˚C)
when running. If this is not the case consult Chapter 7.
CONDENSER
Remove any dust from the condenser fins.
EVERY 4 MONTHS
EVERY 4 MONTHS
COMPRESSOR
COMPRESSOR
Make sure compressor power consumption complies with data plate
specifications.
CONDENSATE DRAIN
YEARLY
Completely disassemble the drain and clean all its components (see
Fig. 8 or separate manual, according to installed drain type).
4
4
English