INSTALLATION INSTRUCTIONS
E-CONOLIGHT BULLET
E-GL5 LED SERIES
CAUTIONS
IMPORTANT SAFEGUARDS
When using electrical equipment, basic safety precautions
should always be followed including the following:
READ AND FOLLOW ALL SAFETY
INSTRUCTIONS
1.
DANGER- Risk of shock- Disconnect power before
installation.
DANGER – Risque de choc – Couper l'alimentation
avant l'installation.
2.
This luminaire must be installed in accordance with the
NEC or your local electrical code. If you are not familiar
with these codes and requirements, consult a qualified
electrician.
Ce produit doit être installé conformément à NEC ou
votre code électrique local. Si vous n'êtes pas familier
avec ces codes et ces exigences, veuillez contacter un
électricien qualifié.
3.
Suitable for mounting within 1.2 m (4 ft) of the ground.
Peut être installé à moins de 1,2 m (4 pi) du sol.
4. Suitable for wet locations.
Convient aux emplacements mouilles.
5.
For supply wire temperature rating, refer to fixture label.
SAVE THESE INSTRUCTIONS FOR
FUTURE REFERENCE
NOTES:
1. When mounting the fixture in an inverted position (1/2" fitter
above fixture), mount fixture to a watertight junction box and
cover. Also, caulk the conduit openings, around the junction box
cover, and the wire entry end of the 1/2" fitter with a high grade
caulking material, such as silicone rubber, to ensure water does
not enter fixture through 1/2" fitter.
www.e-conolight.com
|
Document:
LPN00460X0001A3_A
Created By:
TMT
1.
Do not wire fixture until fixture is mounted.
2.
This fixture can be mounted to any metal ½" NPSM (pipe size)
threaded mounting (supplied by others).
3.
Route fixture leads through the mounting hole.
4.
Thread mounting onto end of fitter on fixture and secure with
locknut. Using a sealing compound on the threads will ensure a
watertight seal.
5.
Complete the electrical connections (see "Fixture Wiring" below).
Fixture is equipped with universal volt driver 120-277V
(ie. 120V, 208V, 240V or 277V)
PHASE TO NEUTRAL WIRING 120/277V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply common to fixture neutral (white) lead.
3. Connect supply Vin to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
PHASE TO PHASE WIRING 208/240V
1. Connect supply ground to fixture ground (green) lead.
2. Connect supply L1 (Hot) to fixture neutral (white) lead.
3. Connect supply L2 (Hot) to fixture hot (black) lead.
Tuck all wires carefully into wiring chamber ensuring that no wires
are pinched.
1.
Loosen the side bolt connected to the arm knuckle to aim the
fixture up or down. Re-tighten bolt to secure the fixture in the
desired position.
FCC NOTICE Class A
CAUTION: Changes or modifications not expressly approved could
void your authority to use this equipment.
This device complies with part 15 of the FCC Rules. Operation is
subject to the following two conditions: (1) This device may not cause
harmful interference, and (2) this device must accept any interference
received, including interference that may cause undesired operation.
This equipment has been tested and found to comply with the limits
for a Class A digital device, pursuant to part 15 of the FCC Rules.
These limits are designed to provide reasonable protection against
harmful interference when the equipment is operated in a commercial
environment. This equipment generates, uses, and can radiate radio
frequency energy and, if not installed and used in accordance with
the instruction manual, may cause harmful interference to radio
communications. Operation of this equipment in a residential area
is likely to cause harmful interference in which case the user will be
required to correct the interference at his own expense.
CAN ICES-005 (A)/NMB-005 (A)
888.243.9445
|
FAX: 262.504.5409
Date
ECO#
MOUNTING
FIXTURE WIRING
TO AIM FIXTURE
2018-5-3
009166

Publicité

loading

Sommaire des Matières pour e-conolight E-GL5 LED Serie

  • Page 1 Date 2018-5-3 INSTALLATION INSTRUCTIONS Created By: ECO# 009166 E-CONOLIGHT BULLET E-GL5 LED SERIES MOUNTING Do not wire fixture until fixture is mounted. This fixture can be mounted to any metal ½” NPSM (pipe size) threaded mounting (supplied by others). Route fixture leads through the mounting hole.
  • Page 2 Fecha 2018-5-08 INSTRUCCIONES DE INSTALACIÓN Creado por: 009166 LUMINARIA E-CONOLIGHT BULLET SERIES E-GL5 LED MONTAJE No instale el cableado hasta que la luminaria esté instalada. Esta luminaria se puede instalar en cualquier montura roscada metálica (tipo tubo) de 1/2” NPSM (suministrada por terceros).
  • Page 3 à corrige l’interférence à ses propres frais. travers le montant de 13 mm (1/2 po). CAN ICES-005 (A)/NMB-005 (A) www.e-conolight.com 888.243.9445 FAX: 262.504.5409...