DETECTEURS Z1 OU Z2 OU Z3 ACTIVENT L'EXTINCTION AUTOMATIQUE
C16
DETECTEURS Z1 ACTIVENT L'EXTINCTION AUTOMATIQUE
C17
DETECTEURS Z2 ACTIVENT L'EXTINCTION AUTOMATIQUE
C18
DETECTEURS Z3 ACTIVENT L'EXTINCTION AUTOMATIQUE
C19
DESACTIVER LE BUZZER D'INCENDIE
C21*
C22*
DESACTIVER LA SORTIE INCENDIE
C23
DESACTIVER LA SORTIE DEFAUT
C24
DESACTIVER LE CONTROLE DES DEFAUTS A LA TERRE
C25
SORTIE DE TELECOMMANDE A IMPULSIONS R0V
C26
COUPURE 24V AUX SUR RESET CENTRALE
C27
SIGNALER EXTINCTION QUAND SORTIE ACTIVEE
PAS D'ACTIVATION DE LA TEMORISATION PAR DECLENCHEMENT
C28
MANUEL
C29
LA SORTIE EXTINCTION PEUT ÊTRE RÉINITIALISÉE EN COURS DE
TEMPORISATION
C2A
LE RELAIS D'INCENDIE LOCAL FONCTIONNE SUR LE SIGNAL
EXTINCTION
EXTINCTION ACTIVE JUSQU'AU RESET
C2b*
C2C
CONTACT PRESSION BASSE NORMALLEMENT FERME
C2d
TEMPORISATION DEFAUT SECTEUR DE 30 MINUTES
C31
ALARME DE ZONE 1 PROVENANT DU DETECTEUR TEMPORISEE
C32
ALARME DE ZONE 2 PROVENANT DU DETECTEUR TEMPORISE
C33
ALARME DE ZONE 3 PROVENANT DU DETECTEUR TEMPORISE
C41
ALARME DE ZONE 1 PROVENANT DU DÉCLENCHEUR MANUEL
C42
ALARME DE ZONE 2 PROVENANT DU DÉCLENCHEUR MANUEL
C43
ALARME DE ZONE 3 PROVENANT DU DÉCLENCHEUR MANUEL
C61
CONFIGURER Z1 POUR LA BARRIERE A SECURITE INTRINSEQUE
C62
CONFIGURER Z2 POUR LA BARRIERE A SECURITE INTRINSEQUE
C63
CONFIGURER Z3 POUR LA BARRIERE A SECURITE INTRINSEQUE
LE COURT-CIRCUIT DE ZONE 1 INDIQUE L'ALARME
C71*
LE COURT-CIRCUIT DE ZONE 2 INDIQUE L'ALARME
C72*
LE COURT-CIRCUIT DE ZONE 3 INDIQUE L'ALARME
C73*
C81*
ZONE 1 SANS VERROUILLAGE
C82*
ZONE 2 SANS VERROUILLAGE
C83*
ZONE 3 SANS VERROUILLAGE
CA1
TOUTE ALARME DE ZONE 1 TEMPORISEE DURANT 30 SECONDES
CA2
TOUTE ALARME DE ZONE 2 TEMPORISEE DURANT 30 SECONDES
CA3
TOUTE ALARME DE ZONE 2 TEMPORISEE DURANT 30 SECONDES
E00
CENTRALE PEUT ETRE RAZ IMMEDIATEMENT APRES QUE LA SORTIE
DECHARGE EST ETE ACTIVEE
E01
CENTRALE PEUT ETRE RAZ DE 1 A 29 MINUTES APRES QUE LA
TO
SORTIE DECHARGE EST ETE ACTIVEE
E29
E30
CENTRALE PEUT ETRE RAZ 30 MINUTES APRES QUE LA SORTIE
DECHARGE EST ETE ACTIVEE
-00
EXTINCTION IMMEDIATE
-05
5 SECONDES AVANT EXTINCTION
-10
INCREMENTATION PAR PAS DE 5 SECONDES TEMPO EXTINCTION
TO
-55
-60
TEMPORISATION DE 60 SECONDES
DUREE SEQUENCE D'EXTINCTION EN SECONDES
060
060
INCREMENTATION PAR PAS DE 5 SECONDES DE LA SEQUENCE
D'EXTINCTION
TO
295
DUREE SEQUENCE D'EXTINCTION EN SECONDES
300
RQUE: le réglage de l'option C15 marquée avec des astérisques n'est pas conforme à EN12094-1
Man-1088 Sigma XT_24
Page 39 sur 42