Kit
Item
Stages
1024166
1
25A @ 240V, 22A @ 277V, 125 VA Pilot Duty
1024167
2
1.
Remove 1/2" single knockout located in front face of cabinet. Reference the figure above for location.
2.
Install thermostat body onto the inside surface of the cabinet front face with the shaft extending through the hole
created in step (1). Orient thermostat so that the capillary points towards the component mounting subpanel. Install
using the two supplied machine screws.
3.
Pull capillary directly down from thermostat body and clamp to component mounting subpanel by screwing the
supplied clip into the mounting hole marked 'T'.
4.
Remove the 1/2" single knockout located in the back face of the cabinet. Reference the figure below for location.
5.
Route the capillary and thermostat bulb through the 1/2" hole created in step (4) and secure the bulb to the external
surface of the back of the heater cabinet using the supplied clip as shown below. Coil any excess capillary inside the
heater wiring compartment.
6.
Install the thermostat lead wires to the screws on the control wiring board per the diagram below and torque screws
to 12 in-lb (1.4 Nm).
7.
Install the "Warmer" knob onto the thermostat shaft.
INDEECO 425 Hanley Industrial Court • St. Louis, Missouri • 63144 • USA
INSTALLATION INSTRUCTIONS-
BUILT ON ROOM THERMOSTAT
UHIR Series Electric Unit Heater
Accessory kit installations should be performed by a qualified electrician.
Risk of electric shock. Disconnect all power supplies before working on
Electrical
Rating
(314) 644-4300 • FAX (314) 644-5332 •
ACCESSORY KITS
WARNING
equipment.
For Use With Heater Model Numbers
All UHIR heaters without option code 'X'
All UHIR heaters with option code 'X'
www.indeeco.com
ENM-2
074-01 / 24-2238-83-1EF

Publicité

loading

Sommaire des Matières pour Indeeco UHIR Serie

  • Page 1 Install the thermostat lead wires to the screws on the control wiring board per the diagram below and torque screws to 12 in-lb (1.4 Nm). Install the “Warmer” knob onto the thermostat shaft. INDEECO 425 Hanley Industrial Court • St. Louis, Missouri • 63144 • USA (314) 644-4300 • FAX (314) 644-5332 • www.indeeco.com...
  • Page 2 à 12 in-lb (1.4 Nm). Montez le bouton “Warmer” (plus chaud) sur l’arbre du thermostat. INDEECO 425 Hanley Industrial Court • St. Louis, Missouri • 63144 • USA (314) 644-4300 • FAX (314) 644-5332 • www.indeeco.com...