saia-burgess ALD1D5FM Instructions De Montage Et D'utilisation page 10

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

Value information field (VIF)
Provides information on multiplier and the unit of the following data block
Value information field extension (VIFE)
Detailed information on multiplier and the unit of the following data block
Data information field (DIF)
Specifies how the data should be interpreted by the master in terms of length and encoding
Data information field extension (DIFE)
Provides information on the tariff or subunits of the following data block
Reading meter
Query:
REQ_UD2
Response:
RSP_UD (see Telegram structure)
Telegram structure
0x68
0x38
02
ACC
0x04
Epa
0xFF
0x01
0xFF
0x01
Variable at 1, 2 or 4 bytes
Byte
Content
23 - 26
Eto=x
30 - 33
Epa=x
39 - 40
V=x
46 - 47
I=x
52 - 53
P=x
59 - 60
Pr=x
I
(Current)
U
(Voltage)
P
(Power)
active
P
(Reactive Power)
reactive
E
(Consumption)
0x38
0x68
0x08
STAT
0
0
0x02
0xFD
0xC9
I
0x02
0xAC
Pr
CSum
0x16
Unit with multiplier
PAdr
0x72
0x8c
0x10
0xFF
0x01
0xFF
0x01
Type
4 b. BCD
4 b. BCD
2b. Integer
2b. Integer
2b. Integer
2b. Integer
ID
0x43
0x4c
0x04
Eto
0x8c
V
0x02
0xFD
P
0x82
0x40
Description
Energy total
Energy partial
Voltage
Current
Power
Reactive Power
ALD1
0.1
1
0.01
0.01
0.01
DEV
0x11
0xDB
0xAC
[ A ]
[ V ]
[ kW ]
[ kVAR ]
[ kWh ]

Publicité