Registres Modbus - Sentera Controls VFSC9 Instructions De Montage Et Mode D'emploi

Variateur électronique
Table des Matières

Publicité

VFSC9
VARIATEUR ÉLECTRONIQUE
NUMÉRIQUE

REGISTRES MODBUS

INPUT REGISTERS
Data type
30001
Output value
unsigned int.
Minimum value of
30002
unsigned int.
PWM duty cycle
Maximum value of
30003
unsigned int.
PWM duty cycle
30004
Input mode
unsigned int.
30005
Work mode
unsigned int.
HOLDING REGISTERS
40001
Device slave address
40002
Modbus baud rate
40003
Modbus parity mode
40004
Device type
40005
HW version
40006
FW version
40007
40008
Overwrite mode
40009
40010
Modbus registers reset
Minimum value of PWM
40011
duty cycle
Maximum value of PWM
40012
duty cycle
40013
Input mode
40014
Analog input mode
40015
Off level
40016
Acceleration
40017
Deceleration
40018-
40019
Network bus terminator
40020
(NBT)
40021
Overwrite value
Pour en savoir plus à propos de Modbus sur liaison série, s'il vous plaît visitez:
MIW-VFSC9-25-FR-000 - 14 / 08 / 18
Description
Output value (PWM duty cycle) in %
Minimum value of PWM duty cycle in %
Maximum value of PWM duty cycle in %
Active input
Current work mode
Data type
Description
unsigned int. Modbus device address
unsigned int. Modbus communication baud rate
unsigned int. Parity check mode
unsigned int. Device type (Read only)
Hardware version of the device (Read
unsigned int.
only)
Firmware version of the device (Read
unsigned int.
only)
unsigned int. Reserved, returns 0
unsigned int. Overwrite mode selection
Reserved, returns 0
Resets all Modbus registers to default
unsigned int.
values (except registers 1—3)
Sets minimum PWM duty cycle value in
unsigned int.
percentage
Sets maximum PWM duty cycle value in
unsigned int.
percentage
unsigned int. Selects active input
unsigned int. Selects analog input mode
unsigned int. Sets OFF level value
unsigned int. Sets acceleration speed
unsigned int. Sets deceleration speed
Reserved, return 0
Sets unit as first or last unit on the line by
unsigned int.
connecting the NBT resistor
PWM duty cycle value (Overwrite mode)
unsigned int.
in percentage
www.sentera.eu
Retour à la Table des matières
Data
Values
0—90
20— 65
145 =
70—90
1—2
0—2
Data
Default
1—247
0—5
0 = 8N1
1 = 8E1
2 = 8O1
3012
XXXX
XXXX
0—1
0—1
20—65
40
70—90
90
0—2
0—2
0; 10—40
0—10
1—10
1—1 0
0; 20—90 60
http://www.modbus.org/docs/Modbus_over_serial_line_V1_02.pdf
80 =
80 =
1 =
Entrée analogique
2 =
External potentiometer input
0 =
1 =
2 =
ALARM / TK
Values
1
0 =
4.800 bps
1 =
9.600 bps
2 =
19.200 bps
2
3 =
38.400 bps
4 =
57.600 bps
5 =
115.200 bps
0 =
1
1 =
2 =
3012 =
VFSC9-XX
0 x 0100 =
HW version 1.00
0 x 0200 =
FW version 2.00
0 =
0
1 =
0 =
0
1 =
45 =
45% PWM
80 =
80% PWM
0 =
Entrée analogique
0
1 =
External potentiometer
2 =
0 =
Voltage mode (0—10 VDC)
0
1 =
Current mode (0—20 mA)
2 =
PWM mode (100%)
0 =
Without Off level
0
10 =
10 % of input → ON
1 =
minimum acceleration
5
10 =
maximum acceleration
1 =
minimum deceleration
5
10 =
maximum deceleration
Disconnected (NBT open)
0 =
Connected (NBT
1 =
connected)
50 =
50 % PWM
80%
45 %
80%h
STOP
RUN
None
Even
Odd
Inactive
Active
Idle
Reset
Auto
input
11 - 12