Listed below the ADVANCED PARAMETERS for the configuration of the inverter
ADV
d 0.40
MF 50
LF30
HF 50
Td 10
PF .50
TPF 0
TP10
TF 3
RF 4

ADVANCED PARAMETERS

Sets the difference between the
selected pressure (SETPOINT)
and the effective restart pressure
Sets the nominal frequency of the
motor
The set value MUST be the same
as the value indicated on the
motor plate
Sets the minimum operating
frequency
Sets the maximum operation
frequency.
CAUTION!! Increasing the
maximum frequency above the
nominal frequency may cause
significant motor overload.
Sets the pump stop delay under
dry running conditions
CAUTION: high values of the stop
delay may damage the pump
Sets the minimum value for the
power factor below which the inverter
stops the pump.
By setting the minimum power factor
value, read the value of the motor
running with closed valves and
deducting 0.03 to it;
Sets the time delay before the
drive will perform the minimum
power factor alarm.
Setting the value to 0 (zero)
disables this feature.
Sets the interval between two
successive automatic attempts to
restart following stops for "dry
running"
Setting the value to "0" excludes
attempts for automatic restarts
Sets the pump stop delay under
no flow conditions
Sets the inverter response speed
to pressure changes
The response value selected
depends on the characteristics of
the system