5.2.4

Thermal derating

The high power outputs allow a maximum output current
of up to 4 amps at pin 2 (X00...X07) with thermal derating.
Fig. 5-4:
Thermal derating curve
5.2.5

Grounding

To counteract EMC interference, the functional earth
connection must be used.
► Connect the earth terminal to the functional earth (FE)
of the machine.
The FE connection between the housing and
the machine must have a low impedance and
be as short as possible.
► Use the grounding strap included in the
scope of delivery.
Fig. 5-5:
Ground connection
www.balluff.com
Ambient temperature in °C
5.3

Cable routing

Cable length
The Ethernet cable may be max. 100 meters long.
The IO-Link single-ended cordset may be max. 20 meters
long.
english
13