C554A Cadmium Sulfide Flame Detector
APPLICATION
The C554A Cadmium Sulfide Flame Detector (cad cell) is
a photoconductive flame detector (see Fig. 1) used with oil
primary controls such as R4166, R4184, R8182, R8184,
R8185, R8404 and R8991. It consists of a plug-in, light
sensitive cell and a socket with Type E mounting bracket,
factory-installed leadwire and an oil line adapter bracket.
Leadwire length is 60 in. (1520 mm). The detector is
installed inside the air tube of the burner where the cell can
view the flame and is wired to the F-F terminals of the oil
primary control.
The photocell is a ceramic disk coated with cadmium
sulfide and overlaid with a conductive grid. Electrodes
attached to the ceramic disk transmit an electrical signal to
the primary control. In darkness, cadmium sulfide has a
very high resistance to the passage of electrical current. In
visible light, its resistance is very low and current is
allowed to pass. The entire cell is hermetically sealed
(glass to metal) to prevent cell deterioration.
SOCKET
PLUG-IN-CELL
Fig. 1. C554A Cadmium Sulfide Flame Detector
(cad cell).
INSTALLATION
When Installing this Product...
1. Read these instructions carefully. Failure to follow
them could damage the product or cause a hazard-
ous condition.
2. Check the ratings given in the instructions and on
the product to make sure the product is suitable for
your application.
3. Installer must be a trained, experienced service
technician.
4. After installation is complete, check out product
operation as provided in these instructions.
®U.S. Registered Trademark
Copyright © 1996 Honeywell Inc. • All Rights Reserved
LEADWIRE
MOUNTING
BRACKET
M7854
INSTALLATION INSTRUCTIONS
CAUTION
Disconnect power supply before beginning
installation to prevent electrical shock or equipment
damage.
Location
The burner manufacturer determines the the cad cell
location (see Fig. 2). If an alternate location must be used,
make sure that:
³ The cell has a clear view of the flame.
· Ambient light does not reach the cell.
» Ambient temperature at the cell location is below
140°F (60°C).
¿ Movement, shielding, or radiation of metal surfaces
located near the cell do not affect cell operation.
CAD CELL
IGNITION
ELECTRODE
AIR TUBE
NOZZLE
Fig. 2. Cad cell location.
Mounting
Direct Replacement
³ Remove the cell from the socket.
· Insert the mounting bracket into the socket slot
(Fig. 3) as far as it will go.
NOTE: Bend the mounting bracket to fit, if
necessary.
X-XX UL
IGNITION
TRANSFORMER
M7857
60-0164B-1

Publicité

loading

Sommaire des Matières pour Honeywell TRADELINE C554A

  • Page 1 NOTE: Bend the mounting bracket to fit, if 3. Installer must be a trained, experienced service necessary. technician. 4. After installation is complete, check out product operation as provided in these instructions. ®U.S. Registered Trademark 60-0164B-1 Copyright © 1996 Honeywell Inc. • All Rights Reserved X-XX UL...
  • Page 2 C554A CADMIUM SULFIDE FLAME DETECTOR » While holding the mounting bracket in the slot, insert Oil Line Mounting the screwdriver in the other end of the slot (Fig. 4). If desired, mount the C554A on the oil line using the oil line Bend the screwdriver, first to the left and then to the adapter bracket and the mounting bracket supplied.
  • Page 3 Fig. 5. Use oil line adapter bracket to specified, recheck the wiring and location mount C554A on oil line. of the cell. If necessary, replace the plug-in part of the cell, Honeywell part no. 130367 Wiring Replacement Cad Cell. Disconnect power supply before beginning wiring to ¿...
  • Page 4 C554A CADMIUM SULFIDE FLAME DETECTOR Automation and Control Solutions Honeywell International Inc. Honeywell Limited-Honeywell Limitée 1985 Douglas Drive North 35 Dynamic Drive Golden Valley, MN 55422 Scarborough, Ontario M1V 4Z9 60-0164B—1 60-0164B—1 J.S. 3-96...
  • Page 5: Montage

    3. L’installateur doit être un technicien d’expérience ayant reçu une formation pertinente. 4. Une fois l’installation terminée, vérifier le fonctionnement de l’appareil comme l’indiquent les présentes directives. ®Marque déposée aur États-Unis 60-0164B-1 60-0164B—1 Copyright © 1996 Honeywell Inc. • Tous droits réservés X-XX UL...
  • Page 6: Raccordement

    Commander la mazout. Pousser fermement pour bloquer la cellule pièce n° 130367 de Honeywell. et le support en place. ¶ Installer le support d’adaptation pour canalisation de mazout sur la canalisation de mazout au moyen de la vis et de l’écrou fournis (voir la Fig.
  • Page 7 DÉTECTEUR DE FLAMME À CELLULE PHOTOCONDUCTRICE C554A C554A CADMIUM SULFIDE FLAME DETECTOR PRISE TOURNEVIS SUPPORT SUPPORT PRISE INSÉRER LE TOURNEVIS ET LE DÉPLACER DANS LE SENS INDIQUÉ PAR LES FLÈCHES POUR FIXER LE SUPPORT DANS LA PRISE CONDUCTEUR FENTE TOURNEVIS MF7855 Fig.
  • Page 8 C554A CADMIUM SULFIDE FLAME DETECTOR Groupe de la Régulation Résidentielle et Commerciale Honeywell Limited-Honeywell Limitée Honeywell International Inc. 35, Dynamic Drive 1985 Douglas Drive North Scarborough (Ontario) M1V 4Z9 Golden Valley, MN 554228 60-0164B—1 60-0164B—1 J.S. 3-96...