Read and understand this manual and all safety signs before using this appliance. Keep
this manual for future reference.
DESCRIPTION
Mini single-channel changeover relay module (for stand-alone and Velbus operation).
USAGE AND CONFIGURATION
The VMB1RYS can be used as a stand-alone changeover relay (with an external input for
switching the relay), or as part of a Velbus system (1 relay, 4 virtual relays, and 1
pushbutton channel).
A. Stand-Alone Mode (factory default)
By factory default, the VMB1RYS is in stand-alone mode. In stand-alone mode, a button
connected to the external input directly controls the relay. Select the operation mode
(toggle or pushbutton) using the MODE/TERM switch on the back (see instructions on
the module sticker). In "toggle" mode, the external input will control the relay in an ON-
OFF mode (each time the input is closed, the relay will switch from open to closed and
vice versa). In "pushbutton" mode, the external input will control the relay in an (ON)-
OFF mode (only while the input is closed, the relay is closed too, otherwise it remains
open).
STATUS LED:
• off: NO open, NC closed
• on: NO closed, NC open
• 3 flashes, pause, 3 flashes, etc.: supply voltage too low
PS LED: supply voltage detected
Rx-Tx LED: not applicable
B. Velbus Mode
To use the VMB1RYS as part of a Velbus system, connect it to a Velbus bus cable with at
least one other Velbus module and configure it using the Velbus configuration software
VelbusLink. (For more information on the Velbus system, go to www.velbus.eu.) By
changing the VMB1RYS's electronic address from FF(HEX)/255(DEC) to any other valid
value (01-253 DEC), Velbus mode is activated. In Velbus mode, the external input no
longer directly controls the relay, but instead both can be configured using the Velbus
configuration software VelbusLink. In Velbus mode, the MODE/TEMP switch on the back
selects the position of the CAN bus terminator (open or closed).
To return the VMB1RYS to standalone mode, reset the electronic address to
FF(HEX)/255(DEC) using the Velbus configuration software VelbusLink.
STATUS LED:
• off: NO open, NC closed
• on: NO closed, NC open
• slow flashing: timer is running
• 2 flashes, pause, 2 flashes, etc: communication error
• 3 flashes, pause, 3 flashes, etc.: supply voltage too low
PS LED: supply voltage detected
Rx LED: CAN bus package received
Tx LED: CAN bus package sent
TECHNICAL SPECIFICATIONS
Relay max. load:
• resistive: 10 A @ 230 VAC / 10 A @ 30 VDC
• capacitive: 6 A @ 230 VAC
• inductive: 6 A @ 230 VAC
• voltage range: 0-250 VAC, 0-30 VDC
Operating conditions: -10 °C to +55 °C
Supply voltage: 15 ± 3 VDC
Max. current consumption: 50 mA
Dimensions: 37 x 57 x 19 mm (L x W x D)
Protection rating: IP10
Number of Velbus channels: 6 (1 relay, 4 virtual relays, 1 external input)
For a complete list of technical specifications, see the product page at www.velbus.eu.
Velbus – Legen Heirweg 33, BE-9890 Gavere, Belgium – tel. +32 9 384 36 11 – e-mail: info@velbus.eu – www.velbus.eu
ENGLISH
CONNECTION DIAGRAMS
A. Stand-Alone Mode (factory default)
B. Velbus Mode
This product complies with all of the relevant European guidelines and
regulations.
This symbol on the device or the package indicates that disposal of the
device after its lifecycle could harm the environment. Do not dispose of
the unit (or batteries) as unsorted municipal waste; it should be taken
to a specialized company for recycling. This device should be returned
to your distributor or to a local recycling service. Respect the local
environmental rules.