Intended use
The FT2018/FT2019 tabular annunciator enables the fire
detection system to be displayed and operated in a
simplified way. The FT2018 provides 2×16 LEDs to
display alarm/trouble events. The FT2019 provides 2×32
LEDs to display alarm/trouble events. Both devices are
operated on the UFP line.
Package contents
FT2018-U1/FT2018-R1 or FT2019-U1/FT2019-R1
l
Cable ties (2 pcs)
l
EOL jumper connecter (1 pcs)
l
Safety instructions
Risk of injury to people and damage to property
Please observe the following safety instructions:
The devices are only intended for stationary installation
l
in dry rooms.
The devices can only be connected to UFP line.
l
If panel auxiliary power is not used, an UL
l
listed/recognized for fire use, regulated, power limited
24 V c.c. power supply is required.
Take static discharge when using the FT2018/FT2019.
l
Legend
Stub for mounting cover (2 pcs.)
1
2
Shield terminal
3
Earth ground terminal
4
Mounting holes (8 pcs.)
5
Cable tie point
6
Cable entries (2 pcs.)
7
Holes for hanging front panel over stub (2 pcs.)
8
Dip-switch
9
Screws (2 pcs.)
10 EOL jumper
11 Connection terminals for UFP line and power supply
12 Front panel earth ground connection
A6V11269908_----_c
All manuals and user guides at all-guides.com
Mounting instruction
1.
2.
3.
4.
5.
6.
7.
8.
9.
Dip-switch
8-digit Dip-switch is used for setting address and baud rate.
The first 1-4 digits are for setting address and the 7, 8 digits
are for setting UFP communication baud rate. The 5 and 6
digits are reserved for future use.
Add.
Technical data
Weight
Dimensions (W x H x D)
(In: inch)
Storage temperature
Operating temperature
Humidity
Housing
Operating voltage
Operating current
(quiescent)
Action current
Break the required cable entries (6) on the backbox.
Mark the drilling points for the 3 mounting holes (4), drill
the holes and insert the anchors (not supplied); or use
the pre-drilled mounting holes for installation on a 1
gang, 2 gang, or 4" square standard electrical box.
Pull the cables for the UFP and power supply, through
the breakout openings (6) on the backbox.
Screw the backbox tightly in place.
Connect the cable to the terminal (11) in accordance
with the connection diagram.
Configure Dip-switch (8) and EOL jumper (10).
Connect the green earth ground cable from front panel
(12) to backbox (3).
Hook the front panel with the holes (7) over the stubs (1)
on the backbox.
Press the front panel down over the backbox, screw (9)
upwards and fix the front panel in place.
Dip-switch
1
2
3
4
1
On Off Off Off
2
Off On Off Off
3
On On Off Off
4
Off Off On Off
5
On Off On Off
6
Off On On Off
7
On On On Off
8
Off Off Off On
Dip-switch
Baud Rate
7
9600 bps
Off
Off
19200 bps
On
Off
38400 bps
Off
On
57600 bps
On
On
FT2018
FT2019
3.064 lb
4.021 lb
8.110x7.362
11.417x7.362
x1.949
x1.949
14...140 °F
32...120.2 °F
≤93% rel.
IP30
24 VCD Nominal
18.8...27.2 VCD
25 mA
25 mA
65 mA
105 mA
8
2