*829768-00*
829768-00
Option Board
The RDB4 option board is to be used with the LP250 power supply when additional features are required. These features include a
distribution of 4 controllable outputs. Each output can be individually configured as powered NO/NC outputs or dry (isolated) NO/NC
outputs.
This instruction covers:
RDB4 Specifications:
Inputs I1 - I4
Outputs O1 - O4
Environment
Compliance
Definitions
Normally closed contacts (NC)
Normally open contacts (NO)
FSE -
Fail secure (needs power to unlock)
RDB4
RDB4 board + mounting screws (4)
Dry contacts required (Closed = Active), rated at 12/24 VDC, 10mA
Powered jumper setting: 12/24 VDC, 2.5A
Dry jumper setting: 30 VDC, 2.5A, NO/NC Form C contacts
11.7 - 12 VDC (13.2V nominal) or 23.4 - 24 VDC (26.4V nominal)
32°-120° F (0°- 49° C), up to 85% relative humidity, indoor use only, protected area
UL294, CSA22.2 NO. 205, CSFM, FCC
FACP - Fire Alarm Control Panel
ACC -
Access Control Contacts
FS -
Fail safe (needs power to lock)
Installation Instructions
See Section 7 for an explanation
of the Warnings and Cautions
used in this booklet.

Publicité

Table des Matières
loading

Sommaire des Matières pour Locknetics RDB4

  • Page 1 Installation Instructions The RDB4 option board is to be used with the LP250 power supply when additional features are required. These features include a distribution of 4 controllable outputs. Each output can be individually configured as powered NO/NC outputs or dry (isolated) NO/NC outputs.
  • Page 2: Output Led's And Output Jumpers

    Mounted in upright position PS board (already installed) Interior of enclosure 6-32 x 1/4" (4) RDB4 - Features and Operation Output LED’s and Output Jumpers OUTPUT JUMPER INPUT OUTPUT NC to GND: DC+ out Powered Jumpers SC to I: open...
  • Page 3 Typical Wiring (see pages 4-6) Wiring methods shall be applied in accordance with the National Electric Code/NFPA 70/NFPA 72/ANSI, and with all local codes and authorities having jurisdiction. WARNING To avoid risk of electric shock, turn off AC power before installing or servicing LP150/LP250 power supply.
  • Page 4 ZONE Operation: Operation: 1. All outputs on the RDB4 are powered and controlled by their individual ACC 1. All power to RDB4 NC/NO outputs is completely cut off when FACP contacts contacts. open. Any devices connected to them will return to their unpowered state.
  • Page 5 2. FA RESET contacts must be momentarily closed (and FACP contacts closed) contacts are open. Outputs 3 and 4 have normal function and will not change if before power can be applied to the RDB4 board. Once power is applied, the RDB4 FACP contacts are open.
  • Page 6 Blank Wiring Diagram Blank diagram for customer use CONTROL CONTROL LP250 ZONE ZONE RDB4 ZONE ZONE...
  • Page 7 Wire run lengths • Use the following table to estimate the gauge of wire required for the application. • Wire length based on 15% voltage drop at 12 or 24V using stranded copper wire. • The wire gauge listed is a minimum. The gauge can be increased if desired. •...
  • Page 8: Warnings And Cautions

    Maintenance Unit should be tested at least once a year for proper operation as follows: Voltage Output: • Verify the proper DC output voltage by measuring the DC+ and DC- terminals. Fire Alarm Release (if used): • Verify proper operation by opening the wiring to the CONTROL IN input. Confirm that all locks on outputs controlled by the CONTROL OUT unlock properly.
  • Page 9: Ces Instructions Couvrent

    Tableau d’options Instructions d’installation La carte optionnelle RDB4 doit être utilisée avec l’alimentation LP250 lorsque des fonctionnalités supplémentaires sont requises. Ces fonctionnalités incluent une distribution de 4 sorties contrôlables. Chaque sortie peut être configurée individuellement en tant que sorties NO / NC alimentées ou sorties NO / NC sèches (isolées).
  • Page 10: Installation Du Rdb4

    Installation du RDB4 ATTENTION Pour éviter tout risque d'électrocution, coupez l'alimentation électrique avant d'installer ou de câbler la carte optionnelle. Vue en coupe du boîtier pour plus de clarté Installez en position verticale Carte PS (déjà installée) Intérieur de l'enceinte...
  • Page 11: Led De Sortie Et Cavaliers De Sortie

    RDB4 - Caractéristiques et fonctionnement LED de sortie et cavaliers de sortie I1 NO1 C1 NC1 I2 NO2 C2 NC2 I3 NO3 C3 NC3 I4 NO4 C4 NC4 BORNE DE SORTIE ENTRÉE SORTIE NC à GND: DC + sortie Contact Cavaliers Normalement fermé...
  • Page 12: Dispositif Fs & Fse Connecté Au Rdb4 Avec Neutralisation Facp (Coupure De Courant)

    ZONE Opération : Opération : 1. Toutes les sorties du RDB4 sont alimentées et contrôlées par leurs contacts ACC 1. Toute alimentation à sorties RDB4 NC/NO est complètement coupée lorsque individuels. FACP est ouvert. Tous les périphériques qui y sont connectés reviendront à leur 2.
  • Page 13: Câblage Typique - Facp

    2. Les contacts FA RESET doivent être momentanément fermés (et les contacts lorsque les contacts FACP sont ouverts. Les sorties 3 et 4 ont une fonction FACP fermés) avant de pouvoir alimenter la carte RDB4. Une fois que le courant normale et ne changeront pas si les contacts FACP sont ouverts.
  • Page 14: Schéma De Câblage Vierge

    Schéma de câblage vierge Diagramme vierge à l'usage du client ENTRÉE DES CONTRÔLES SORTIE DES LP250 CONTRÔLES SORTIE NOIR ROUGE ZONE ZONE RDB4 ZONE ZONE...
  • Page 15: Longueurs De Fil

    Longueurs de fil • Utilisez le tableau suivant pour estimer le calibre de fil requis pour l’application. • Longueur de fil basée sur une chute de tension de 15 % à 12 ou 24 V avec un fil de cuivre toronné. •...
  • Page 16: Entretien

    Entretien L’unité doit être testée au moins une fois par an pour vérifier son bon fonctionnement, comme suit: Tension de sortie: • Vérifiez la tension de sortie CC appropriée en mesurant les bornes DC + et DC-. Déclenchement d’alarme incendie (si utilisé): •...