PC5108 v2.0 Installation Instructions
8-Zone Expander Module
This Installation sheet shall be used in conjunction with the Installation Manual of the
DSC equipment to which PC5108 is connected or powered from (e.g. alarm controller,
power supply, etc.). The PC5108 module can be used to extend up to 8 hardwired input
zones on the compatible DSC Alarm Controllers, models PC5010, PC5015, PC5020,
PC1864, PC1832 and PC1616.
General
This product meets the requirements of Class II, Grade 2 equipment as per EN50131-
1:1997 and prEN50131-1:2004 Standards.
PC5108 may be installed in the same metallic cabinet as the alarm controller/power
supply (model Power UC1, PC5003C) or in a separate enclosure (PC4003C). Internal
and/or external wiring for the PC5108 shall be routed, supported, clamped or secured in
a manner that reduces the likelihood of (a) excessive strain on wire and terminal connec-
tions, (b) loosening of terminal connections, and (c) damage of conductor insulation.
Specifications
•Temperature range: -10°C to + 55°C
•Relative Humidity: 93% non condensing
•Input rating: 12V
/135mA (provided by the alarm controller or separate power supply)
DC
•Board current draw: 35mA (set and unset state)
•Board dimensions: 45mm x 92mm
•VAUX output ratings: 12V
, -15%/ +10% when Input voltage is between 85%
DC
to110% of rated value and output current is between 0mA- 100mA max.
•Resettable fuse (PTC) used on circuit board instead of replaceable fuses
Terminal Descriptions
VAUX 12V
,
DC
A 100mA
Power Limited
Used to tamper the cabinet in which the PC5108 is mounted. Connect a nor-
TAM -
mally closed (NC) switch across TAM and BLK. If the tamper is not being used connect a
piece of wire across TAM and BLK to remove the trouble condition.
29007166R004
There is a built-in tamper switch on the expander module located in the top left corner
of the circuit board. If the cabinet in which the PC5108 is mounted has the hardware
required to depress this tamper switch, do not connect anything to the TAM terminal.
- Used to provide power for devices. Maximum current draw is not to exceed 100
VAUX
mA. Connect the positive lead of powered devices to VAUX and the negative to BLK or
any COM terminal.
- The 4-wire Keybus connection is used by the panel to communicate with the
KEYBUS
module. Connect the RED, BLK, YEL and GRN terminals to the KEYBUS terminals on the
PC1616, PC1832, PC1864, PC5010, PC5015 & PC5020 main control.
- Wire the zones according to the description found in the control panel
Z1 to Z8
Installation Manual.
Enclosures
The PC5108 can be installed in the metal enclosures listed below. Tamper protection
switches can be installed on all enclosures, including door opening protection and/or
removal from the mounting position. Doors can be secured using screws or keylock.
• Model PC5003C (removable door) made of 22Ga steel, painted.
Dimensions: 248mm(L) x 298mm(W) x 76mm(H), Weight: 1500g.
• Model PC5003C (hinged door) made of 1.2mm thick steel, painted.
Dimensions: 248mm(L) x 298mm(W) x 76mm(H), Weight: 2500g
• Model Power UC1 made of 18Ga steel, painted.
Dimensions: 315mm(L) x 319mm(W) x 100mm(H), Weight: 3150g.
• Model PC4003C made of 18Ga steel, painted
Dimensions: 230mm(L) x 180mm(W) x 75mm(D), Weight: 1050g.
Jumper Settings
The PC5108 module can be used to add up to 8 additional hardwired zones to the
PC1616, PC1832, PC1864, PC5010, PC5015 or PC5020 control panel (see Installation
Manual for complete installation instructions).
Jumpers
Expander Zones
On control panels with software
Group A (Zones1-8)
versions 3.x and higher, the
Group B (not used)
PC5108 v2.0 will operate in a
single group of eight zones.
Refer to the following jumper
settings:
On control panels with software
Expander Zones
versions 2.x and lower, the
Group A (Zones1-4)
PC5108 v2.0 will operate in
Group B (Zones 5-8)
two groups of four zones. Refer
to the following jumper set-
tings:
To Add Hardwired Zones to a Control Panel
1. Connect module to the Keybus (with the panel powered down).
2. Set the jumpers on the module.
3. Power up the system.
4. Enter section [902] and wait 1 minute.
5. Enter section [903] to verify that the module is supervised.
6. Define the zones in sections [002]-[004], [109]-[164] for PC1616, PC1832,
PC1864, PC5010, or PC5020.
7. Add the zones to the appropriate partition in sections [202]-[265].
LIMITED WARRANTY
Digital Security Controls warrants that for a period of twelve months from the date of pur-
chase, the product shall be free of defects in materials and workmanship under normal use
and that in fulfilment of any breach of such warranty, Digital Security Controls shall, at its
option, repair or replace the defective equipment upon return of the equipment to its factory.
This warranty applies only to defects in parts and workmanship and not to damage incurred
in shipping or handling, or damage due to causes beyond the control of Digital Security
Controls such as lightning, excessive voltage, mechanical shock, water damage, or damage
arising out of abuse, alteration or improper application of the equipment.
The foregoing warranty shall apply only to the original buyer, and is and shall be in lieu of
any and all other warranties, whether expressed or implied and of all other obligations or
liabilities on the part of Digital Security Controls. This warranty contains the entire war-
ranty. Digital Security Controls neither assumes responsibility for, nor authorizes any other
person purporting to act on its behalf to modify or to change this warranty, nor to assume
for it any other warranty or liability concerning this product. In no event shall Digital Secu-
rity Controls be liable for any direct or indirect or consequential damages, loss of antici-
pated profits, loss of time or any other losses incurred by the buyer in connection with the
purchase, installation or operation or failure of this product.
Warning: Digital Security Controls recommends that the entire system be completely
tested on a regular basis. However, despite frequent testing, and due to, but not limited
to, criminal tampering or electrical disruption, it is possible for this product to fail to
perform as expected.
FCC COMPLIANCE STATEMENT
CAUTION: Changes or modifications not expressly approved by Digital Security
Controls could void your authority to use this equipment.
This equipment generates and uses radio frequency energy and if not installed and used
properly, in strict accordance with the manufacturer's instructions, may cause interfer-
Jumpers
Zones Assigned
ence to radio and television reception. It has been type tested and found to comply with
J1
J2
J3
the limits for Class B device in accordance with the specifications in Subpart "B" of Part
15 of FCC Rules, which are designed to provide reasonable protection against such inter-
ON ON ON Zones Disabled
ference in any residential installation. However, there is no guarantee that interference
OFF ON ON Zones 9-16
will not occur in a particular installation. If this equipment does cause interference to
ON OFF ON Zones 17-24
television or radio reception, which can be determined by turning the equipment off and
OFF OFF ON Zones 25-32
on, the user is encouraged to try to correct the interference by one or more of the follow-
ON ON OFF Zones 33-40
ing measures:
• Re-orient the receiving antenna
OFF ON OFF Zones 41-48
• Relocate the alarm control with respect to the receiver
ON OFF OFF Zones 49-56
• Move the alarm control away from the receiver
OFF OFF OFF Zones 57-64
• Connect the alarm control into a different outlet so that alarm control and receiver are
on different circuits.
Jumpers
Zones Assigned
If necessary, the user should consult the dealer or an experienced radio/television techni-
J1
J2
J3
cian for additional suggestions. The user may find the following booklet prepared by the
FCC useful: "How to Identify and Resolve Radio/Television Interference Problems".
J4
J5
J6
This booklet is available from the U.S. Government Printing Office, Washington D.C.
ON ON ON Zones Disabled
20402, Stock # 004-000-00345-4.
OFF ON ON Zones Disabled
ON OFF ON
Zones 9-12
OFF OFF ON
Zones 13-16
ON ON OFF
Zones 17-20
OFF ON OFF
Zones 21-24
ON OFF OFF
Zones 25-28
OFF OFF OFF
Zones 29-32
©2008 Digital Security Controls Toronto, Canada ˘ www.dsc.com
Tech. Support: 1-800-387-3630 (Canada & U.S.), 905-760-3036
Printed in Canada

Publicité

loading

Sommaire des Matières pour DSC Power Serie PC5108

  • Page 1 Connect the positive lead of powered devices to VAUX and the negative to BLK or 5. Enter section [903] to verify that the module is supervised. DSC equipment to which PC5108 is connected or powered from (e.g. alarm controller, any COM terminal.
  • Page 2 Il ya un interrupteur anti-sabotage sur le module d’extension situé en haut à gauche de la carte à circuit imprimé. Si le coffret utilisé pour installer le module de sortie Imprime au Canada ©2008 Digital Security Controls Toronto, Canada • www.dsc.com Centre d’aide technique : 1-800-387-3630 (Canada/U.S.),ou 905-760-3036...