Periodical Inspection; Checks During Operation - Ferroli DIVA HC24 Instructions D'utilisation, D'installation Et D'entretien

Table des Matières

Publicité

Les langues disponibles

Les langues disponibles

DIVA HC24
C
D
E
G
fig. 10 - Gas valve
A - Protection cap screw
B - Pressure point downstream
C - Modureg cable
D - Protection cap
E - Min. pressure adjustment
G - Max. pressure adjustment
Heating power adjustment
To adjust the heating power, switch the boiler to TEST mode (see sec. 4.1). Press the
heating buttons detail 3 - fig. 1 to increase or decrease the power (min. = 00 - max. =
100). Press the reset button within 5 seconds and the max. power will remain that just
set. Exit TEST mode (see sec. 4.1).
Lighting power adjustment
To adjust the lighting power, switch the boiler to TEST mode (see sec. 4.1). Press the
DHW buttons (detail 1 - fig. 1) to increase or decrease the power (min. = 00 - max. = 60).
Press the reset button within 5 seconds and the lighting power will remain that just set.
Exit TEST mode (see sec. 4.1).
4.2 Startup
Before lighting the boiler
Check the seal of the gas system.
Check correct prefilling of the expansion tank.
Fill the water system and make sure all air contained in the boiler and the system
has been vented.
Make sure there are no water leaks in the system, DHW circuits, connections or boil-
er.
Check correct connection of the electrical system and efficiency of the earthing sys-
tem.
Make sure the gas pressure for heating is that required.
Make sure there are no flammable liquids or materials in the immediate vicinity of
the boiler

Checks during operation

Switch the unit on.
Check the tightness of the fuel circuit and water systems.
Check the efficiency of the flue and air/fume ducts while the boiler is working.
Make sure the water is circulating properly between the boiler and the systems.
Make sure the gas valve modulates correctly in the heating and domestic hot water
production stages.
Check correct boiler lighting by performing various tests, turning it on and off with
the room thermostat or remote control.
Make sure the fuel consumption indicated on the meter matches that given in the
technical data table in cap. 5.
Make sure that with no demand for heating, the burner lights correctly on opening a
hot water tap. Check that in heating mode, on opening a hot water tap, the heating
circulating pump stops and there is regular production of hot water.
Make sure the parameters are programmed correctly and carry out any required
customisation (compensation curve, power, temperatures, etc.).
All manuals and user guides at all-guides.com
4.3 Maintenance

Periodical inspection

To ensure proper operation of the unit over time, have qualified personnel carry out a
yearly inspection, providing for the following checks:
A
B
C
D
4.4 Troubleshooting
Diagnostics
The boiler is equipped with an advanced self-diagnosis system. In case of a boiler fault,
the display will flash together with the fault symbol (detail 11 - fig. 1) indicating the fault
code.
There are faults that cause permanent shutdown (marked with the letter "A"): to restore
operation, press the RESET button (detail 6 - fig. 1) for 1 second or RESET on the op-
tional remote timer control if installed; if the boiler fails to start, it is necessary to eliminate
the fault.
Faults marked with the letter "F" cause temporary shutdowns that are automatically reset
as soon as the value returns within the boiler's normal working range.
Table of faults
Table. 2 - List of faults
cod. 3541E901 - Rev. 00 - 12/2015
The control and safety devices (gas valve, flow switch, thermostats, etc.) must func-
tion correctly.
The fume exhaust circuit must be perfectly efficient.
(Sealed chamber boiler: fan, pressure switch, etc. - The sealed chamber must be
tight: seals, cable glands, etc.)
(Open chamber boiler: anti-backflow device, fume thermostat, etc.)
The air/fume terminal and ducts must be free of obstructions and leaks
The burner and exchanger must be clean and free of deposits. Do not use chemical
products or wire brushes to clean.
The electrode must be properly positioned and free of deposits.
=
=
fig. 11 - Electrode positioning
The gas and water systems must be tight.
The pressure of the water in the system when cold must be approx. 1 bar; otherwise,
bring it to that value.
The circulating pump must not be blocked.
The expansion tank must be filled.
The gas flow and pressure must match that given in the respective tables.
Fault
Fault
Possible cause
code
No gas
Ignition/detection
electrode fault
A01
No burner ignition
Faulty gas valve
Ignition power too
low
Electrode fault
Flame present signal with
A02
burner off
Card fault
Heating sensor
damaged
Overtemperature protection
A03
No water circulation
activation
in the system
Air in the system
Fume thermostat
Fume thermostat activated
contact open
(after activation of the fume
F04
Wiring disconnected Check the wiring
thermostat, boiler operation is
Flue obstructed or
prevented for 20 minutes)
not correctly sized
Wrong card parame-
F05
Card parameter fault
ter setting
Low pressure in the
gas system
No flame after the ignition
A06
phase
Burner minimum
pressure setting
Cure
Check the regular gas flow to the
boiler and that the air has been elim-
inated from the pipes
Check the wiring of the electrode
and that it is correctly positioned and
free of any deposits
Check the gas valve and replace it if
necessary
Adjust the ignition power
Check the ionisation electrode wir-
ing
Check the card
Check the correct positioning and
operation of the heating sensor
Check the circulating pump
Vent the system
Check the thermostat
Check the flue
Check the card parameter and mod-
ify it if necessary
Check the gas pressure
Check the gas pressures
EN