Installation Guide, LE system
DK
LE System
Bemærk!
Den ønskede funktion, undgåelse af dråbedannelse, kan kun
opnås ved anvendelse af både LE-pumpe og LE-dyse eller LE-
ventil.
LE-pumper har en anden typebetegnelse end standard BFP 21
pumper, f.eks. BFP 21 L3 LE, og adskiller sig ved at have en ind-
bygget nippel med returventil og en omstillingsskrue.
Bemærk! Standard BFP 21 pumper kan ikke ombygges til BFP
21 LE-pumper!
LE-funktion
Drejes omstillingsskruen venstre om mod stop, er LE-funktio-
nen indkoblet. Drejes omstillingsskruen højre om mod stop, er
LE-funktionen udkoblet, og pumpen fungerer som en standard
BFP 21 pumpe.
LE-funktionen skal udkobles, hvis:
- LE-dysen erstattes af en standard dyse
- LE-ventilen fjernes
Forfilter
LE-systemer kræver et effektivt forfilter:
LE-1 system: Maks. 40 μm
LE-2 system: Standard forfilter
Tekniske data
Standard fyringsolie og fyringsolie
Olietyper
iht. DIN V 51603-6 EL A Bio 10
Viskositetsområde
1,8-12,0 mm
Omdrejningstal
Trykområde
Fabriksindstilling
Spolespænding
Spolens kapsling
Medietemperatur
Ved LE-1 system er der et trykfald over LE-dysen på 1,6 bar, som
der skal korrigeres for ved indstilling af pumpetrykket.
Eksempel:
Ønsket dysetryk 10,0 bar (kPa 102)
Pumpetryk: 10,0 + 1,6 bar = 11,6 bar (kPa 102)
Ved LE-2 system er der et trykfald over LE-ventilen på maks. 0,1
bar.
Pumpetrykket behøver derfor ikke at blive korrigeret.
Udluftning
Udluftning af oliepumpen er kun nødvendig ved 1-strengs
anlæg. Udluftning foretages gennem manometerstudsen P!
Ved 2-strengs anlæg udlufter pumpen automatisk gennem
returledningen.
Filterskift (fig. 2)
Filterproppen i dækslet skrues ud med en 4 mm nøgle og
patronfilteret trækkes ud. Sæt evt. en skruetrækker imellem
filter og prop og vrid forsigtigt filteret af. Filteret kasseres og er-
stattes med et nyt, som presses på proppen!
Patronfilteret genmonteres og spændes let til.
Husk udskiftning af O-ring.
Omstilling fra 1- og 2-strengs drift (fig. 3)
Sugeledningslængder i meter
Tabellerne gælder for en standard fyringsgasolie (Heizöl-
EL) normal handelskvalitet iht. gældende normer.
Ved igangsætning af et anlæg med tomt rørsystem bør
oliepumpen ikke køre uden olie i mere end 5 minutter.
Henvisning!
Oliepumperne er kun beregnet for anvendelse på oliebrænde-
re.
Maks. tilladeligt tryk på suge- og returside: 1,5 bar
Bemærk venligst, at magnetventil og LE-ventil skal
udskiftes efter 250.000 koblinger eller 10 år (godkendt
forventet levetid).
BI.DF.U2.63
LE System
Note!
The required function, avoiding drop formation, can only be
achieved by using the LE pump together with an LE nozzle or an
LE valve.
LE pumps have been given a new type designation, e.g. BFP 21 L3
LE and differ from standard BFP 21 pumps by having a built-in re-
turn valve with changeover screw.
Note! Standard BFP 21 pumps cannot be converted to BFP 21 LE
pumps!
LE function
If the changeover screw is turned to the left towards stop, the LE
function is engaged. If the change over screw is turned to the right
to stop, the LE function is disengaged and the pump will function
as a standard BFP 21 pump.
The LE function must be disengaged if:
- A standard nozzle is used instead of an LE nozzle.
- The LE valve is removed.
Prefilter
The LE-1 system requires an effective prefilter:
LE-1 system: Max. 40 μm
LE-2 system: Standard prefilter
Technical data
Oil types
Viscosity range
/s (cSt.)
2
Speed
2400-3450 min
–1
Pressure range
7-15 bar (kPa 10²)
Factory setting
10 bar (kPa 10²)
Coil voltage
220/240 V, 50/60 Hz
Coil enclosure
IP 40
Temperature of medium
0 til 70° C
There is a pressure drop in the LE nozzle of 1.6 bar which needs
to be compensated for by adjusting the pump pressure.
Example:
Required nozzle pressure 10.0 bar (kPa 102)
Pump pressure: 10.0 + 1.6 bar = 11.6 bar (kPa 102)
In the LE-2 system, there is a pressure drop of max. 0.1 bar
across the LE valve.
The pump pressure does not need to be adjusted.
Bleeding
Bleeding of the oil pump may be necessary with 1-pipe
systems. Use the pressure gauge connection P for bleeding!
On 2-pipe systems the pump is automatically bleed through
the return pipe.
Filter replacement (fig. 2)
Unscrew the filter plug in the cover with a 4 mm key and pull
out the cartridge filter. Carefully twist the filter out (if necessary
insert a screwdriver between filter and plug).
Scrap the filter and press a new filter onto the plug!
Reassemble the cartridge filter and tighten it lightly.
Don't forget to replace the O-ring.
Conversion from 1 to 2-pipe operation (fig. 3)
Suction line lengths in meters
The table is applicable for a standard gas oil (Heizöl-EL) of
normal commercial quality in accordance with applicable
standards.
When starting a system with an empty pipe, the oil pump
should not operate without oil for more than 5 min. Assuming
that the pump contains some oil before starting up.
Attention
The oil pumps are used only for oil burners.
Max. permissible pres. on suction/return side: 1.5 bar
Please note that the solenoid valve and the LE-valve
must be replaced after 250.000 operations or 10 years
(approved life expectancy).
GB
LE System
Achtung
Der erforderliche Betrieb ohne Tropfenbildung wird nur durch
kombinierten Einsatz der LE-Pumpe mit einer LE-Düse oder ei-
nem LE-Ventil erreicht.
LE-Pumpen verfügen über eine neue Typenkennzeichnung,
z. B. „BFP 21 L3 LE" und unterscheiden sich von Standard-BFP-
21-Pumpen durch ein eingebautes Rückschlagventil mit Um-
stellungsschraube.
Hinweis! Standard-BFP-21-Pumpen können nicht in BFP-21-LE-
Pumpen umgerüstet werden.
LE-Funktion
Wenn die Umstellungsschraube bis zum Anschlag nach links
gedreht wird, wird die LE-Funktion aktiviert. Wenn die Umstel-
lungsschraube bis zum Anschlag nach rechts gedreht wird,
wird die LE-Funktion deaktiviert, und die Pumpe arbeitet als
Standard-BFP-21-Pumpe.
In folgenden Fällen muss die LE-Funktion deaktiviert
werden:
- Anstelle einer LE-Düse wird eine Standarddüse
verwendet.
- Das LE Ventil im Ölvorwärmer wurde entfernt.
Vorfilter
Für das LE-1-System ist ein effektiver Vorfilter erforderlich:
LE-1-System: Max. 40 μm
Standard fuel gas oil and fuel gas oil
LE-2-System: Standard-Vorfilter
acc. to DIN V 51603-6 EL A Bio 10
Technische Daten
1,8-12,0 mm
2
/s (cSt.)
Öltypen
2400-3450 min
–1
7-15 bar (kPa 10²)
Viskositätsbereich
10 bar (kPa 10²)
Drehzahl
220/240 V, 50/60 Hz
IP 40
Druckbereich
Werkseinstellung
0 to 70° C
Spulenspannung
Schutzart der Spule
Medientemperatur
In der LE-Düse fällt der Druck um 1,6 bar ab. Dieser Druckabfall
muss durch Anpassung des Pumpendrucks ausgeglichen wer-
den.
Beispiel:
Erforderlicher Düsendruck: 10,0 bar (kPa 102)
Pumpendruck: 10,0 + 1,6 bar = 11,6 bar (kPa 102)
Im LE-2-System fällt der Druck im LE-Ventil um maximal 0,1 bar
ab.
Eine Anpassung des Pumpendrucks ist nicht erforderlich.
Entlüftung
Die Entlüftung der Ölpumpe ist nur bei Einstranganlagen
notwendig. Die Entlüftung wird durch den Manometerstutzen
P vorgenommen. In Zweistranganlagen entlüftet die Pumpe
automatisch über die Rücklaufleitung.
Filterwechsel (Abb.2)
Filterschraube im Deckel mit einem 4 mm Inbus-Schlüssel lösen
und Patronenfilter heraus ziehen.
Evtl. einen Schraubendreher zwischen Filter und Schraube zum
Lösen des Filters stecken. Einen neuen Filter auf die Schraube
pressen! Patronenfilter montieren und leicht anziehen.
Wechseln des O-Ringes nicht vergessen.
Umstellung von Ein- auf Zweistrangbetrieb (Abb.3).
Saugrohrlängen in Meter
Die Tabellen sind für Qualitätsheizöl (Heizöl-EL) einer normalen
Handelsqualität nach geltenden Normen gültig.
Bei der Inbetriebnahme einer Anlage mit leerem Rohrsystem
sollte die Ölpumpe nicht länger als 5 Minuten ohne Öl betrie-
ben werden, vorausgesetzt, dass vor der Inbetriebnahme Öl in
der Pumpe ist.
Hinweis!
Die Ölpumpen sind ausschließlich für Ölbrenner vorgesehen!
Max. zul. Druck auf Saug-u.Rucklaufseite:1,5 bar
Achtung: Das NC-Magnetventil und das LE Ventil im Ölvorwär-
mer müssen nach 250.000 Schaltungen oder 10 Jahren ausge-
tauscht werden (geprüfte Lebensdauererwartung).
DE
Standard Heizöl und Heizöl gemäβ
DIN V 51603-6 EL A Bio 10
1,8-12,0 mm
/s (cSt.)
2
2400-3450 min
–1
7-15 bar (kPa 10²)
10 bar (kPa 10²)
220/240 V, 50/60 Hz
IP 40
0 bis 70° C
© Danfoss | 2019.04 | 3