Télécharger Imprimer la page

Danfoss AK-PS 075 Manuel D'instructions page 2

Publicité

Connection / Connecting cable
To achieve a reliable and shockproof connection, strip the connecting ends according to table 1!
Tabelle 1
Starr
Flexibel
Table 1
Solid
Stranded
Tableau 1
Rigide
Souple
Tabla 1:
Rigido
Flexible
2
[mm
]
[mm
1 1 1 1 2 2 2 2
0,2-2,5
0,2-2,5
Fuse
For device protection, there is an internal fuse
(250 V AC / 125 V d.c.):
AK-PS 075 = 1.25 AT
AK-PS 150 = 1.25 AT
AK-PS 250 = 3.15 AT
LED
On
Normal operation of the
power supply
Load Table AK I/O Modules
The AK-PS ___ has an output rating to power I/O devices in any combination. Refer to table below for individual
I/O device power requirements.
Module name
AK-CM 101_ / 102_
AK-XM 101_
AK-XM 102_
AK-XM 103_
AK-XM 107_
AK-XM 204_
AK-XM 205_
AK-XM 208_
AK-CC_ / PC_ ...
2
Instructions
50
61
Abb./Fig. 2
Anzugsmoment
Torque
Couple de serrage
Par de apriete
2
]
AWG
[Nm]
[lb in]
24-12
0,6-0,8
5-7
© PHOENIX CONTACT 2007
1. The output voltage is less than 21.5 V. There is a secondary consumer short circuit
or overload.
2. There is no input voltage or there is a device fault
Description
Communications module
Universal input module
Digital input module
(low voltage) / (high voltage)
Universal input module &
analog output module
Pulse measuring
Digital output module
Universal analog input &
digital output module
Bipolar stepper output module
AK controller
RI8LJ302
Abb./Fig. 3
Abisolierlänge
Stripping length
Longueur à dénuder
Longitud a desaislar
L [mm]
6,5
Abb./Fig. 4
If the internal fuse is triggered, there is most probably
a malfunction in the device. In this case, the device
must be replaced!
LED
Off
Inputs & Outputs
8 universal inputs
8 digital inputs,
4 universal inputs,
4 analog outputs
8 pulse inputs
8 relay outputs
8 relay outputs,
8 universal inputs
4 bipolar stepper outputs
© Danfoss 4-2017
Power
2 VA
2 VA
2 VA
2 VA
2 VA
5 VA
5 VA
5 VA
8 VA
AK-PS

Publicité

loading

Ce manuel est également adapté pour:

Ak-ps 150Ak-ps 250