Mise en service
Data object
Length [byte]
MANUFACTU-
2
RER_ID
ORDER_ID
20
SERIAL_NUMBER 16
HARDWARE_RE-
2
VISION
SOFTWARE_RE-
4
VISION
REVI-
2
SION_COUNTER
PROFILE_ID
2
PROFILE_SPECI-
2
FIC_TYPE
IM_VERSION
2
IM_SUPPORTED 2
Tableau 8 : I&M 0 (Slot 0, Index 0xAFF0)
Data object
Length [byte]
TAG_FUNCTION
32
TAG_LOCATION
22
Tableau 9 : I&M 1(emplacement 0, Index 0xAFF1)
Data object
Length [byte]
INSTALLATION_-
16
DATE
Tableau 10 : I&M 2(emplacement 0, Index 0xAFF2)
Data object
Length [byte]
DESCRIPTOR
54
Tableau 11 : I&M 3(emplacement 0, Index 0xAFF3)
Data object
Length [byte]
SIGNATURE
54
Tableau 12 : I&M 4(emplacement 0, Index 0xAFF4)
70
6.8 Fonctions d'identification et de
Access
Default value / Description
Read
0x016A (Belden Deutschland
GmbH)
Read
Order number of module in ASCII
Read
Defined in production process in
ASCII
Read
Hardware revision of device
Read
Software revision of device
Read
Est intégré pour chaque modifica-
tion de paramètre enregistrée de
manière statique sur le maître IO-
Link (p. ex. nom de l'équipement,
à savoir Device Name, ou
adresse IP)
Read
0xF600 (Generic device)
Read
0x0003 (modules E/S)
Read
0x0101 (I&M version 1.1)
Read
0x001E (I&M 1...4 is supported)
Access
Default value / Description
Read/Write
0x20 ff. (empty)
Read/Write
0x20 ff. (empty)
Access
Default value / Description
Read/Write
0x20 ff. (empty); Supported data
format is a visible string with a fix
length of 16 byte;
"YYYY-MM-DD hh:mm" or
"YYYY-MM-DD" filled with blank
spaces
Access
Default value / Description
Read/Write
0x20 ff. (empty)
Access
Default value / Description
Read/Write
0x20 ff. (empty)
Manuel technique LioN-P PROFINET IO-Link Master
maintenance (I&M)
Release 2.0 04/2017

Publicité