Configuration of output 1
4 switching functions can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
Configuration of output 2
4 switching functions and 2 analogue signals can be set:
- Hno = hysteresis / normally open
- Hnc = hysteresis / normally closed
- Fno = window function / normally open
- Fnc = window function / normally closed
- I = analogue output 4 ... 20 mA
- U = analogue output 0 ... 10 V
Analogue start point
Measured value at which 4 mA / 0 V is provided.
ASP is active only if OU2 = I or U.
Analogue end point
Measured value at which 20 mA / 10 V is provided.
Minimum distance between ASP and AEP = 25% of the final
value of the measuring range (scaling factor 4).
AEP is active only if OU2 = I or U.
Setting range: → page 46 / 47.
Enhanced functions
This menu item contains a submenu with additional parameters.
You can access these parameters by pressing the SET button
briefly.
Min-Max memory for system pressure
• HI: displays the highest measured pressure
• LO: displays the lowest measured pressure
Erase the memory:
- Press the "Mode/Enter" button until HI or LO is displayed.
- Press the "Set" button and keep it pressed until "- - - -" is
displayed.
- Then press the "Mode/Enter" button briefly.