2. Recommendations for commissioning the burner
a. Ignition electrodes
Check that there is no arc disturbance
Check the gap on the electrodes: 4 mm
• Check the position of the electrode against the black spot: it
must be on A
b. Flame tube and recirculation slit
Check the setting of the recirculation slit (see settings table on
next page)
Do not obstruct the recirculation slit if you have to insulate the
combustion chamber door
Check that the flame tube is correctly attached to the
intermediate tube (bayonet fully engaged)
3