TEMPERATURE PARAMETERS SETTINGS
Sensor type, summer/winter mode, anti-frost, minimum outlet temperature, sensor deviation correction
and external sensor activation.
Temperature reference selection between outlet and
room sensor.
Winter/Summer mode. If summer is selected,
heating system is disabled even if there is a sud-
den temperature drop. Only anti-frost system will
remain active.
Anti-frost protection. This system is normally used for water coil versions to avoid risk of
freezing. If selected temperature is reached, the fault output relay is activated together with the
activation of water valve (if installed, not included). If temperature continues dropping, the fans
will stop working and an audible alarm will be activated and the logo will appear on the control
display. In case of ambient sensor installed and enabled, take into account that control will au-
tomatically take into account the selected ambient temperature +3°C.
Minimum outlet temperature. Regardless all sensor values and setpoints, the air curtain will
maintain this minimum air outlet temperature.
Sensor deviation correction. If sensor is installed in an inappropriate location for architectural
or space reasons, readings offered can be corrected manually.
External sensor activation. Apart from displaying this value on the screen, you can also choose
this parameter as a reference for automatic control.
DOOR CONTACT ADJUSTMENTS
Door contact activation, contact type parameterization and run-on-timer.
Door contact activation. With this function and through a door
contact not included (accessory CR-MAGNET COR-PRO), it
will be possible to see on the main screen of the control whe-
ther the door is opened or closed. Unless Automatic Mode A
is active, the curtain will turn off with a delay once the door
closes. The contact is a potential free type and maximum load
is 24VDC/3A.
Door contact position. Function that allows to defi ne door contact as normally open
or closed
.
Run-on-timer when contact disconnection. Once the door contact detects that the door is clo-
sed, it initiates a recommended timing period to dissipate internal heat. It is recommended not
to confi gure a value lower than the factory-set 60s. This function remains active only if the door
contact function has been activated. If automatic mode A is active, this timing is disabled.
Door contact and control valve position. Function only for water coil versions. Selecting OFF,
when the door is closed, ensures that the valve closes regardless of whether or not thermal
support is required depending on the difference between the selected and measured tempera-
tures. Selecting ON, when the door is closed, keeps the valve in position depending on the eva-
luation of the required controller temperature, that is, the valve is kept open (in case heating is
requested from the controller temperature requirements set and temperatures measured in the
sensor) or closed (if there is no need for thermal support according to selected and measured
temperature).